Plan Review Notes
Plan Review Notes For Permit 20090244
Permit Number 20090244
Review Stop B
Sequence Number 4
Notes
Date Text
2020-10-26 10:43:37RESIDENTIAL (R3) REROOF BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL30268-R1
 SUBMITTED:
 SELECTED ASSEMBLY W-1 CAN NOT BE USED. THIS ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES AS
 REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. BONDED
 ASSEMBLIES NEED TO MEET THE DESIGN PRESSURES FOR ALL
 ROOF ZONES. SEE NOTE #10 ON PAGE 2 OF 45 OF PRODUCT
 APPROVAL SUBMITTED.
 NEED TO SELECT ANOTHER BONDED ASSEMBLY THAT MEETS THE
 DESIGN PRESSURES FOR ALL ROOF ZONES REQUIRED BY SEC.
 R301.2.1 FBC-RESIDENTIAL. OR SELECT ANOTHER
 MECHANICALLY FASTENED ASSEMBLY THAT MEETS THE DESIGN
 FOR ALL ROOF ZONES. OR SELECT ANOTHER ASSEMBLY THAT
 ALLOWS NAIL ENHANCEMENT BY DOING RAS 117 CALCULATIONS.
 IF RAS 117 CALCULATIONS ARE PROVIDED, THEN THEY NEED TO
 BE PROPERLY SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL.
  
 2- REPEAT COMMENT FROM PREVIOUS PLAN REVIEWERS. NO
 CLEAR WHY SUBMITTING PRODUCT APPROVALS FOR SHINGLES.
 ACCORDING TO PALM BEACH COUNTY PROPERTY APPRAISER THERE
 ARE ONLY FLAT ROOFS ON THE TWO STRUCTURE ON THIS
 PROPERTY. REVISE/CLARIFY AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]