| 2020-10-26 10:43:37 | RESIDENTIAL (R3) REROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL30268-R1 |
| | SUBMITTED: |
| | SELECTED ASSEMBLY W-1 CAN NOT BE USED. THIS ASSEMBLY |
| | DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES AS |
| | REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. BONDED |
| | ASSEMBLIES NEED TO MEET THE DESIGN PRESSURES FOR ALL |
| | ROOF ZONES. SEE NOTE #10 ON PAGE 2 OF 45 OF PRODUCT |
| | APPROVAL SUBMITTED. |
| | NEED TO SELECT ANOTHER BONDED ASSEMBLY THAT MEETS THE |
| | DESIGN PRESSURES FOR ALL ROOF ZONES REQUIRED BY SEC. |
| | R301.2.1 FBC-RESIDENTIAL. OR SELECT ANOTHER |
| | MECHANICALLY FASTENED ASSEMBLY THAT MEETS THE DESIGN |
| | FOR ALL ROOF ZONES. OR SELECT ANOTHER ASSEMBLY THAT |
| | ALLOWS NAIL ENHANCEMENT BY DOING RAS 117 CALCULATIONS. |
| | IF RAS 117 CALCULATIONS ARE PROVIDED, THEN THEY NEED TO |
| | BE PROPERLY SIGNED AND SEALED BY THE DESIGN |
| | PROFESSIONAL. |
| | |
| | 2- REPEAT COMMENT FROM PREVIOUS PLAN REVIEWERS. NO |
| | CLEAR WHY SUBMITTING PRODUCT APPROVALS FOR SHINGLES. |
| | ACCORDING TO PALM BEACH COUNTY PROPERTY APPRAISER THERE |
| | ARE ONLY FLAT ROOFS ON THE TWO STRUCTURE ON THIS |
| | PROPERTY. REVISE/CLARIFY AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |