| 2020-12-28 09:36:58 | PLAN REVIEW / NFIP |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | CITY ORDINANCE NO. 4658-16 |
| | |
| | 4TH REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. |
| | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN |
| | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER |
| | PREVIOUS COMMENTS. |
| | |
| | |
| | RE: CONSTRUCTION DRAWING ELEVATION CERTIFICATE (EC) |
| | |
| | 1. CORRECTED |
| | |
| | 2. ORIGINAL SIGNATURE OF SURVEYOR IS REQUIRED. (NOT |
| | CORRECTED) (SEE COMMENTS IN SIGNATURE REVIEW) |
| | |
| | NEW COMMENTS: |
| | |
| | 3. CORRECTED |
| | |
| | NEW COMMENTS: |
| | |
| | 4. REF: SECTION A9 OF EC AND PLAN PAGE A-101 FOR THE |
| | FOLLOWING: |
| | |
| | SECTION A9(A) STATES SQ/FT OF GARAGE IS 519 SF. |
| | SECTION A9(B) STATES NUMBER OF FLOOD OPENINGS IS 2. |
| | SECTION A9(C) STATES TOTAL NET AREA OF FLOOD OPENINGS |
| | IN A9(B) IS 256 SQ/IN. |
| | |
| | PLAN PAGE A-101 STATES 2 SMART VENTS 8X16 INCHES WILL |
| | BE INSTALLED AND EACH VENT IS CERTIFIED FOR 400 SF. |
| | |
| | REF: PRODUCT APPROVAL FL 5822-R7: |
| | VENT MODELS THAT ARE 8X16 INCHES MAY ONLY BE USED FOR |
| | UP TO 200 SQ/FT OF INTERIOR SPACE. |
| | VENT MODELS THAT MAY BE USED FOR UP TO 400 SQ/FT OF |
| | INTERIOR SPACE ARE 16X16 INCHES (STACKABLE) |
| | |
| | SECTION A9 OF THE EC AND PLAN PAGE A-1.01 ARE IN |
| | CONFLICT. |
| | |
| | PLEASE SELECT MODEL OR MODELS OF VENTS TO BE INSTALLED |
| | FROM PRODUCT APPROVAL AND REVISE SECTION A9 OF EC AND |
| | PLAN PAGE A-101. |
| | ALSO PROVIDE INSTALLATION INSTRUCTIONS FOR MODEL OR |
| | MODELS OF VENTS TO BE INSTALLED. |
| | |
| | |
| | PROVISOS ON PLAN PAGE A-101. |
| | 1. PROVIDE BUILDING UNDER CONSTRUCTION ELEVATION |
| | CERTIFICATE TO CITY INSPECTOR AT PLACEMENT OF 1ST |
| | FLOOR. |
| | 2. PROVIDE FINISHED CONSTRUCTION ELEVATION CERTIFICATE |
| | PRIOR TO C/O. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |