| Date |
Text |
| 2020-12-17 09:42:47 | PLAN REVIEW / NFIP |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | CITY ORDINANCE NO. 4658-16 |
| | |
| | 3RD REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. |
| | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN |
| | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER |
| | PREVIOUS COMMENTS. |
| | |
| | |
| | RE: CONSTRUCTION DRAWING ELEVATION CERTIFICATE (EC) |
| | |
| | 1. REF. LINE A5 OF EC. LATITUDE IS STATED AS 39 33 81 |
| | N. GOOGLE MAPS/GOOGLE EARTH SHOWS THE LATITUDE FOR 6175 |
| | S FLAGLER AS 26 39 24 N. PLEASE CORRECT LATITUDE. |
| | CORRECTED |
| | |
| | |
| | 2. ORIGINAL SIGNATURE OF SURVEYOR IS REQUIRED. (NOT |
| | CORRECTED) |
| | |
| | A SCAN OF A WET SEAL AND SIGNATURE OR DIGITAL SIGNATURE |
| | IS NOT CONSIDERED A DIGITAL SIGNATURE. |
| | |
| | EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR DROP |
| | OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL WET |
| | SEAL AND SIGNATURE TO: |
| | |
| | BUILDING DIVISION, FIRST FLOOR |
| | CITY OF WEST PALM BEACH |
| | 401 CLEMATIS ST |
| | WEST PALM BEACH, FL 33401 |
| | |
| | NEW COMMENTS: |
| | |
| | 3. . FLOOD VENTS SHALL BE INSTALLED ON ADJACENT WALLS |
| | OF ENCLOSED AREAS. SUBMIT NEW PLAN PAGES THAT SHOW THE |
| | LOCATION OF THE VENTS. |
| | R322.2.2.1INSTALLATION OF OPENINGS. T |
| | THE WALLS OF ENCLOSED AREAS SHALL HAVE OPENINGS |
| | INSTALLED SUCH THAT: |
| | 1. 1.THERE SHALL BE NOT LESS THAN TWO OPENINGS ON |
| | DIFFERENT SIDES OF EACH ENCLOSED AREA; IF A BUILDING |
| | HAS MORE THAN ONE ENCLOSED AREA BELOW THE DESIGN FLOOD |
| | ELEVATION, EACH AREA SHALL HAVE OPENINGS. |
| | 2. 2.THE BOTTOM OF EACH OPENING SHALL BE NOT MORE THAN |
| | 1 FOOT (305 MM) ABOVE THE HIGHER OF THE FINAL INTERIOR |
| | GRADE OR FLOOR AND THE FINISHED EXTERIOR GRADE |
| | IMMEDIATELY UNDER EACH OPENING. |
| | 3. 3.OPENINGS SHALL BE PERMITTED TO BE INSTALLED IN |
| | DOORS AND WINDOWS; DOORS AND WINDOWS WITHOUT INSTALLED |
| | OPENINGS DO NOT MEET THE REQUIREMENTS OF THIS SECTION. |
| | ALSO SEE SEC. 4.1 OF THE ICC-ES REPORT FOR VENT |
| | LOCATION. |
| | ALSO SEE FEMA TECHNICAL BULLETIN #1 - FLOOD OPENINGS IN |
| | WALLS. |
| | |
| | NOTICE: PROVIDE BUILDING UNDER CONSTRUCTION ELEVATION |
| | CERTIFICATE TO CITY INSPECTOR AT PLACEMENT OF 1ST |
| | FLOOR. |
| | PROVIDE FINISHED CONSTRUCTION ELEVATION CERTIFICATE |
| | PRIOR TO C/O. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |
| | |
| | |