| 2020-12-17 09:04:43 | PLAN REVIEW / BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NEC 2014 |
| | |
| | 3RD REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PROVISO: GENERATOR SHALL BE BY SEPERATE PERMIT. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. |
| | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN |
| | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER |
| | PREVIOUS COMMENTS. |
| | |
| | 1. ALL PLAN SHEETS HAVE AN INCORRECT ADDRESS. (101 |
| | SANTA LUCIA DRIVE). THE CORRECT ADDRESS IS 6175 S |
| | FLAGLER DRIVE. PLEASE CORRECT AND RE-SUBMIT. (NOT |
| | CORRECTED) |
| | |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 2. PROVIDE ICC-ES REPORT AND PRODUCT APPROVALS FOR |
| | SMART VENTS. (ICC-ES REPORT RCV'D. PROVIDE INSTALLATION |
| | INSTRUCTIONS FOR SMART VENT MODEL 1540-511). |
| | |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | NEW COMMENTS: |
| | |
| | 3. REFERENCE YOUR PERMIT REVIEW RESPONSE LTR DATED |
| | 12/11/2020: ALTHOUGH MULTIPLE DOCUMENTS SUCH AS PRODUCT |
| | APPROVALS, NOC, SOILS REPORT, ETC. MAY BE UPLOADED AS |
| | ONE PDF, THE ELEVATION CERTIFICATE MUST BE UPLOADED |
| | SEPERATELY. WE HAVE TO SUBMIT THESE TO FEMA AND NEED A |
| | CLEAN EC WITHOUT ANY ATTACHMENTS. |
| | ALSO, PLEASE FOLLOW THE FILE NAMING GUIDELINES ON THE |
| | QUICK START GUIDE AND PROVIDE THE NAME OF THE DOCUMENTS |
| | INCLUDED IN THE FILE. |
| | IT'S PREFERABLE BUT NOT REQUIRED FOR EACH DOCUMENT TO |
| | BE UPLOADED SEPERATELY WITH IT'S APPROPRIATE NAME. THIS |
| | HELPS THE REVIEW PROCESS TREMENDOUSLY. |
| | |
| | 4. I DO NOT SEE A NEW SURVEY IN THE RESPONSE LTR DOC. |
| | THE SURVEY SHOULD ALSO BE UPLOADED AS A SEPERATE FILE. |
| | |
| | 5. FLOOD VENTS SHALL BE INSTALLED ON ADJACENT WALLS. |
| | SUBMIT NEW PLAN PAGES THAT SHOW THE LOCATION OF THE |
| | VENTS. |
| | R322.2.2.1INSTALLATION OF OPENINGS. |
| | THE WALLS OF ENCLOSED AREAS SHALL HAVE OPENINGS |
| | INSTALLED SUCH THAT: |
| | 1. 1.THERE SHALL BE NOT LESS THAN TWO OPENINGS ON |
| | DIFFERENT SIDES OF EACH ENCLOSED AREA; IF A BUILDING |
| | HAS MORE THAN ONE ENCLOSED AREA BELOW THE DESIGN FLOOD |
| | ELEVATION, EACH AREA SHALL HAVE OPENINGS. |
| | 2. 2.THE BOTTOM OF EACH OPENING SHALL BE NOT MORE THAN |
| | 1 FOOT (305 MM) ABOVE THE HIGHER OF THE FINAL INTERIOR |
| | GRADE OR FLOOR AND THE FINISHED EXTERIOR GRADE |
| | IMMEDIATELY UNDER EACH OPENING. |
| | 3. 3.OPENINGS SHALL BE PERMITTED TO BE INSTALLED IN |
| | DOORS AND WINDOWS; DOORS AND WINDOWS WITHOUT INSTALLED |
| | OPENINGS DO NOT MEET THE REQUIREMENTS OF THIS SECTION. |
| | ALSO SEE SEC. 4.1 OF THE ICC-ES REPORT FOR VENT |
| | LOCATION. |
| | ALSO SEE FEMA TECHNICAL BULLETIN #1 - FLOOD OPENINGS IN |
| | WALLS. |
| | |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |
| | |