| 2020-09-24 10:50:51 | PLAN REVIEW / BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NEC 2014 |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE SOILS REPORT. |
| | FBC 1803.1 GENERAL. GEOTECHNICAL INVESTIGATIONS SHALL |
| | BE CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND |
| | REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE |
| | REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL |
| | INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY |
| | TESTING OR ENGINEERING CALCULATIONS, SUCH |
| | INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED |
| | DESIGN PROFESSIONAL. |
| | R401.4 SOIL TESTS. |
| | WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL |
| | SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE, |
| | SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE |
| | LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL |
| | DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE |
| | THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION. |
| | THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN |
| | APPROVED METHOD. |
| | |
| | 2. STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZRD AREA |
| | (SFHA). ENCLOSED AREAS BELOW THE DESIGN FLOOD ELEVATION |
| | (DFE) REQUIRE FLOOD OPENINGS. LOCATE THE REQUIRED |
| | NUMBER OF FLOOD OPENINGS ON THE FOUNDATION PLAN. |
| | FBC APPENDIX G FLOOD RESISTANT CONSTRUCTION AND |
| | FBC R 322.2.2 ENCLOSURES BELOW DESIGN FLOOD ELEVATION. |
| | |
| | 3. PROVIDE THE ICC EVALUATION SERVICE REPORT FOR THE |
| | PROPOSED ICYNENE SPRAY FOAM INSULATION. |
| | DESIGNER SHALL SELECT THE PRODUCT TO BE INSTALLED TO |
| | ACHIEVE THE REQUIRED R-20 INSULATION VALUE FOR THE ROOF |
| | ASSEMBLY. |
| | PROVIDE THE ICYNENE SPRAY FOAM INSULATION INSTALLATION |
| | INSTRUCTIONS. |
| | INSTALLATION INSTRCUTIONS SHALL BE MADE AVAILABLE TO |
| | THE CITY INSPECTOR FOR INSPECTION. |
| | |
| | 4. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE WINDOW MULLION SUBMITTALS. |
| | |
| | 5. PRODUCT APPROVAL FL16546-R5 IS EXPIRED. PROVIDE |
| | PRODUCT APPROVAL BASED ON THE FBC 6TH EDITION. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE OHD SUBMITTALS. |
| | |
| | 6. DESIGNER SHALL REVIEW AND APPROVE PRODUCT APPROVALS. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |
| | |