| Plan Review Notes For Permit 20090218 |
| Permit Number |
20090218 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-09-23 14:06:15 | SKY LIGHT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) THE PRODUCT CHOSEN IN THE PROVIDED PRODUCT APPROVAL | | | FL11480.2 IS "NON-IMPACT" - THE SKY LIGHT NEEDS TO MEET | | | IMPACT REQUIREMENTS PER FBC R301.2.1.2 | | | 2) SKY LIGHT CANNOT BE WITHIN 4 FOOT OF THE SIDE OF THE | | | FIREWALL BETWEEN TOWNHOUSES FBC R302.2.2 (DRAW THE | | | CENTER LINE BETWEEN TOWNHOUSES AND SHOW THE DISTANCE OF | | | THE SKY LIGHT FROM THE LINEON YOUR ROOF PHOTO - WHICH | | | WOULD BE A MINIMUM OF 4 FEET 4 INCHES FROM THE CENTER | | | LINE AND THE SIDE OF THE SKY LIGHT). | | | | | | | | | | | | |
|