Plan Review Notes
Plan Review Notes For Permit 20090218
Permit Number 20090218
Review Stop B
Sequence Number 1
Notes
Date Text
2020-09-23 14:06:15SKY LIGHT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) THE PRODUCT CHOSEN IN THE PROVIDED PRODUCT APPROVAL
 FL11480.2 IS "NON-IMPACT" - THE SKY LIGHT NEEDS TO MEET
 IMPACT REQUIREMENTS PER FBC R301.2.1.2
 2) SKY LIGHT CANNOT BE WITHIN 4 FOOT OF THE SIDE OF THE
 FIREWALL BETWEEN TOWNHOUSES FBC R302.2.2 (DRAW THE
 CENTER LINE BETWEEN TOWNHOUSES AND SHOW THE DISTANCE OF
 THE SKY LIGHT FROM THE LINEON YOUR ROOF PHOTO - WHICH
 WOULD BE A MINIMUM OF 4 FEET 4 INCHES FROM THE CENTER
 LINE AND THE SIDE OF THE SKY LIGHT).
  
  
  
  