2020-11-13 04:18:40ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 COVER SHEET AND ELECTRICAL SHEET ARE THE SAME PAGE.
  
 1) WALL SPACING FOR OUTLETS.
  
 E3901.2.1 SPACING. RECEPTACLES SHALL BE INSTALLED SO
 THAT NO POINT MEASURED HORIZONTALLY ALONG THE FLOOR
 LINE OF ANY WALL SPACE IS MORE THAN 6 FEET (1829 MM),
 FROM A RECEPTACLE OUTLET. [210.52(A)(1)]
  
 2) SMOKE ALARMS NOT SHOWN.
  
 PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER
 CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 R314.3, FBC 107.2.1