Plan Review Notes
Plan Review Notes For Permit 20090202
Permit Number 20090202
Review Stop B
Sequence Number 2
Notes
Date Text
2020-11-14 09:24:28PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 2ND REVIEW
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 VALUE: 12 X 17 ADDITION. 204 SQ. FT. APPLIED VALUE IS
 $9,000.00. ESTIMATED VALUE BASED ON THE ICC BUILDING
 VALUATION TABLES IS $24,982.00.
  
 1. CITY OF WPB CHPT. 1 VALUE (NO CONTRACT PROVIDED)
 (CALCULATED VALUE PER ICC VALUATION TABLES IS
 $24,982.00 FOR 204 SQ. FT. ADDITION. CREDIT APPLIED
 BASED ON EXISTING EXT. WALLS W/ FOUNDATION AND NO
 PLUMBING WORK IS $7,000.00. VALUE HAS BEEN ADJUSTED TO
 $17,981.00)
  
 109.3 BUILDING PERMIT VALUATIONS.
 1A. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK.
 1B. THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. THIS INCLUDES ALL LABOR,
 MATERIALS AND RENTALS OF EQUIPMENT TO PERFORM THE SCOPE
 OF WORK.
 1C. YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY
 THE OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
 BASED ON THE INFORMATION PROVIDED, VALUE CANNOT BE
 DETERMINED AT THIS TIME.
 PLEASE INCREASE THE VALUATION ACCORDINGLY.
  
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL
  
 2. PROPOSED ADDITION HAS AN EXISTING PATIO SLAB.
 DEMONSTRATE HOW YOU WILL COMPLY WITH BELOW GRADE
 MOISTURE BARRIER REQUIREMENTS PER R406.3.2 AND TERMITE
 TREATMENT REQUIREMENTS PER R318.1.
 (NO TERMITE TREATMENT PROVIDED)
 (NO MOISTURE BARRIER DETAIL PROVIDED)
 ( NOTE #7 ON PLAN PAGE LABLED "WALL FRAMING" STATES
 "BOTTOM PLATE TO HAVE VAPOR BARRIER INSTALLED ON TOP OF
 STEM WALL PRIOR TO INSTALL").
 (PLEASE CLARIFY)
  
 3. THERE IS A STEM WALL DETAIL ON PLAN PAGE S-1. SHOW
 THE LOCATION OF THIS STEM WALL ON PLAN. (DEMO PLAN
 SHOWS STEM WALL AS EXISTING. WHAT IS THE LOCATION OF
 THE STEM WALL DETAIL ON PLAN PAGE S-1)
  
 4. UNDER FLOOR VENTILATION MAY BE REQUIRED IF STEM WALL
 IS USED PER R408.1 (NO CRAWL SPACE VENTILATION DETAIL
 PROVIDED)
  
 5. PLANS USE BUILDING CODE REFERENCES FOR DESIGN.
 PROVIDE CONSTRUCTION DRAWINGS PER 107.2 - CORRECTED
  
 6. PROVIDE A COMPLETE SET OF CONSTRUCTION DRAWINGS: -
 CORRECTED
  
 7. BEDROOM WINDOW SHALL COMPLY WITH EGRESS REQUIREMENTS
 PER R310.2. - CORRECTED
  
 NEW COMMENTS:
  
 8. PLAN PAGE LABLED PROPOSED ELECTRICAL IS A SECOND
 COPY OF THE COVER PAGE. PLEASE CORRECT.
  
 9. ENERGY GUAGE INDICATES R-30 TO BE INSTALLED IN
 CEILING. PLAN PAGE LABLED STUCCO DETAIL INDICATES R-19
 TO BE INSTALLED. PLEASE CLARIFY.
  
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  