| 2020-11-14 09:24:28 | PLAN REVIEW / BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NEC 2014 |
| | |
| | 2ND REVIEW |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. |
| | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN |
| | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER |
| | PREVIOUS COMMENTS. |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | VALUE: 12 X 17 ADDITION. 204 SQ. FT. APPLIED VALUE IS |
| | $9,000.00. ESTIMATED VALUE BASED ON THE ICC BUILDING |
| | VALUATION TABLES IS $24,982.00. |
| | |
| | 1. CITY OF WPB CHPT. 1 VALUE (NO CONTRACT PROVIDED) |
| | (CALCULATED VALUE PER ICC VALUATION TABLES IS |
| | $24,982.00 FOR 204 SQ. FT. ADDITION. CREDIT APPLIED |
| | BASED ON EXISTING EXT. WALLS W/ FOUNDATION AND NO |
| | PLUMBING WORK IS $7,000.00. VALUE HAS BEEN ADJUSTED TO |
| | $17,981.00) |
| | |
| | 109.3 BUILDING PERMIT VALUATIONS. |
| | 1A. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE |
| | OF WORK. |
| | 1B. THE PERMIT VALUATION AND PERMIT FEE MUST BE |
| | COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED |
| | CONTRACTOR WOULD PROVIDE. THIS INCLUDES ALL LABOR, |
| | MATERIALS AND RENTALS OF EQUIPMENT TO PERFORM THE SCOPE |
| | OF WORK. |
| | 1C. YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY |
| | THE OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT |
| | RENTAL TO VERIFY VALUE. |
| | BASED ON THE INFORMATION PROVIDED, VALUE CANNOT BE |
| | DETERMINED AT THIS TIME. |
| | PLEASE INCREASE THE VALUATION ACCORDINGLY. |
| | |
| | FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| | BUILDING OFFICIAL |
| | |
| | 2. PROPOSED ADDITION HAS AN EXISTING PATIO SLAB. |
| | DEMONSTRATE HOW YOU WILL COMPLY WITH BELOW GRADE |
| | MOISTURE BARRIER REQUIREMENTS PER R406.3.2 AND TERMITE |
| | TREATMENT REQUIREMENTS PER R318.1. |
| | (NO TERMITE TREATMENT PROVIDED) |
| | (NO MOISTURE BARRIER DETAIL PROVIDED) |
| | ( NOTE #7 ON PLAN PAGE LABLED "WALL FRAMING" STATES |
| | "BOTTOM PLATE TO HAVE VAPOR BARRIER INSTALLED ON TOP OF |
| | STEM WALL PRIOR TO INSTALL"). |
| | (PLEASE CLARIFY) |
| | |
| | 3. THERE IS A STEM WALL DETAIL ON PLAN PAGE S-1. SHOW |
| | THE LOCATION OF THIS STEM WALL ON PLAN. (DEMO PLAN |
| | SHOWS STEM WALL AS EXISTING. WHAT IS THE LOCATION OF |
| | THE STEM WALL DETAIL ON PLAN PAGE S-1) |
| | |
| | 4. UNDER FLOOR VENTILATION MAY BE REQUIRED IF STEM WALL |
| | IS USED PER R408.1 (NO CRAWL SPACE VENTILATION DETAIL |
| | PROVIDED) |
| | |
| | 5. PLANS USE BUILDING CODE REFERENCES FOR DESIGN. |
| | PROVIDE CONSTRUCTION DRAWINGS PER 107.2 - CORRECTED |
| | |
| | 6. PROVIDE A COMPLETE SET OF CONSTRUCTION DRAWINGS: - |
| | CORRECTED |
| | |
| | 7. BEDROOM WINDOW SHALL COMPLY WITH EGRESS REQUIREMENTS |
| | PER R310.2. - CORRECTED |
| | |
| | NEW COMMENTS: |
| | |
| | 8. PLAN PAGE LABLED PROPOSED ELECTRICAL IS A SECOND |
| | COPY OF THE COVER PAGE. PLEASE CORRECT. |
| | |
| | 9. ENERGY GUAGE INDICATES R-30 TO BE INSTALLED IN |
| | CEILING. PLAN PAGE LABLED STUCCO DETAIL INDICATES R-19 |
| | TO BE INSTALLED. PLEASE CLARIFY. |
| | |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |