Plan Review Notes
Plan Review Notes For Permit 20090195
Permit Number 20090195
Review Stop G
Sequence Number 1
Notes
Date Text
2020-09-28 14:17:1309/14/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE AN ISOMERIC RISER DIAGRAM DRAWING OF
 THE GAS SYSTEM, CLEARLY SHOWS THE LENGTH OF ALL CUT
 SECTIONS OF PIPE, SHOW THE TYPE OF PIPE MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING EHD
 NUMBER OF THE CORRUGATED STAINLESS-STEEL TUBING (IF
 APPLICABLE) FOR EACH PIPE SIZE, SHOW THE DISTANCE FROM
 THE POINT OF DELIVERY TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND/OR SYSTEM, LIST THE BTU LOAD OF EACH
 APPLIANCE, THE TOTAL BTU LOAD OF THE EXISTING SYSTEM,
 DELIVERY PRESSURE (PSI) OF THE SYSTEM AND TYPE OF GAS
 (LP OR NATURAL) PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.3.5.3 (12) RESIDENTIAL GAS.
  
 2. ON PLANS SUBMITTED IT STATE THAT A FUTURE APPLIANCE
 WILL BE AT THE RUN TO BE USED LATER. THIS IS NOT
 PERMITTED UNLESS THE APPLIANCE THAT WILL BE CONNECTED
 IS SUBMIT WITH THIS APPLICATION AND IS APPROVED A VALVE
 AND NIPPLE WILL BE REQUIRED AND WILL NEED TO BE SHOWN
 ON THE ISOMETRIC PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER
 THE 2017 FBC RES. SEC. G2401.1.3.
  
 4. A SUB GAS PERMIT IS REQUIRED FOR THE SCOPE OF WORK
 PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 (CLOTHES DRYER AND RANGE), OR 2017 FBC RES. SEC.
 G2407.1 AND G2439.4.
  
 6. PLEASE SUBMIT THE SIZING TABLE USED IN THE DESIGN
 FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS OF
 PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM PER THE 2017 FBC RES. SEC. G2413.3.
  
 7. A SUB PLUMBING PERMIT IS REQUIRED FOR THE SCOPE OF
 WORK AS A WASHING MACHINE IS SHOWN. THE CITY HAS DONE
 PRIOR INSPECTIONS ON THIS ADDRESS AND A DRAIN FOR A
 WASHING MACHINE WAS REMOVED BECAUSE IT WAS NOT TO CODE,
 PLEASE INCLUDE DOCUMENTATION FOR PERMITTING OF A
 WASHING MACHINE DRAIN PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  