Plan Review Notes
Plan Review Notes For Permit 20090192
Permit Number 20090192
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-09-10 10:42:45THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1 & E 2 - THERE ARE INDICATIONS OF THE THE
 TWO EXISTING BATHROOM DOORS THAT OPEN OUT INTO THE EXIT
 EGRESS CORRIDOR.
  
 THERE IS ALSO AN EXIT SIIGN DIRECTING THE EXIT PATH
 DOWN THAT CORRIDOR.
  
 THOSE DOORS, THOUGH EXISTING, RESTRICT THE REQUIRED
 EGRESS WIDTH.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
  
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR
 LEAF IS FULLY OPEN
  
 PLEASE REVIEW AND CORRECT THE DOOR SWING OR REVIEW THIS
 EXIT SIGN AND PATH AS IT MAY NOT BE REQUIRED. THERE IS
 A POTENTIAL FOR ONE EXIT FROM THE OPEN AREA THROUGH THE
 BREAKROOM.
  
 PER NFPA 101, CH 39EXISTING BUSINESS AND CH 7, MEANS OF
 EGRESS.
  
 39.2.4 NUMBER OF MEANS OF EGRESS.
 39.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE
 FOLLOWING,
 EXCEPT AS OTHERWISE PERMITTED BY 39.2.4.2 THROUGH
 39.2.4.6:
 (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 7.4.1.1 AND 7.4.1.3 THROUGH 7.4.1.6.
 (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED
 ON EVERY
 STORY.
 (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM
 EVERY PART OF EVERY STORY.
 39.2.4.2 EXIT ACCESS, AS REQUIRED BY 39.2.4.1(3), SHALL
 BE PERMITTED
 TO INCLUDE A SINGLE EXIT ACCESS PATH FOR THE DISTANCES
 PERMITTED AS
 COMMON PATHS OF TRAVEL BY 39.2.5.3.
 39.2.4.3 A SINGLE EXIT SHALL BE PERMITTED FOR A ROOM OR
 AREA WITH A
 TOTAL OCCUPANT LOAD OF LESS THAN 100 PERSONS, PROVIDED
 THAT ALL OF
 THE FOLLOWING CRITERIA ARE MET:
 (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE AT
 THE LEVEL OF
 EXIT DISCHARGE FOR THE BUILDING.
 (2) THE TOTAL DISTANCE OF TRAVEL FROM ANY POINT,
 INCLUDING TRAVEL
 WITHIN THE EXIT, SHALL NOT EXCEED 100 FT (30 M).
 (3) THE TOTAL DISTANCE OF TRAVEL SPECIFIED IN
 39.2.4.3(2) SHALL BE
 ON THE SAME STORY, OR, IF TRAVERSING OF STAIRS IS
 NECESSARY, SUCH
 STAIRS SHALL NOT EXCEED 15 FT (4570 MM) IN HEIGHT, AND
 BOTH OF
 THE FOLLOWING ALSO SHALL APPLY:
 (A) INTERIOR STAIRS SHALL BE PROVIDED WITH COMPLETE
 ENCLOSURES TO SEPARATE THEM FROM ANY OTHER PART OF THE
 BUILDING, WITH NO DOOR OPENINGS THEREIN.
 (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2
 SHALL BE
 PERMITTED TO SERVE ALL STORIES PERMITTED WITHIN THE 15
 FT
 (4570 MM) VERTICAL TRAVEL LIMITATION.
  
 PLEASE REVIEW AND PROVIDE A LIFE SAFETY PLAN SHOWING
 TRAVEL DISTANCES THAT WOULD ME THE SINGLEE XIT
 REQUIREMENTS AND REMOVE THE EXIT SIGN AT THE CORRIDOR.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  