| Date |
Text |
| 2020-09-09 16:35:59 | 1ST REVIEW FBC-2017 FUEL GAS |
| | PERMIT- 20090171 |
| | 9/9/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE NEW ACCESSIBLE SHUT OFF VALVE FOR THE RANGE |
| | SHALL BE LOCATED NO MORE THAN 6 FT. FROM THE APPLIANCE- |
| | SECTION 409.5.1 FBC FG. |
| | |
| | 2) SHOW THE LOCATION OF THE AUTOMATIC GAS SHUTOFF VALVE |
| | FOR THE SYSTEM AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS- SECTION 10.4 NFPA 96. |
| | |
| | 10.4.1- UPON ACTUATION OF ANY FIRE-EXTINGUISHING SYSTEM |
| | FOR A COOKING OPERATION, ALL SOURCES OF FUEL AND |
| | ELECTRIC POWER THAT PRODUCE HEAT TO ALL EQUIPMENT |
| | PROTECTED BY THE SYSTEM SHALL AUTOMATICALLY SHUT OFF. |
| | |
| | 3) THE GAS RANGE IS INDICATED AS EXISTING UNDER THE |
| | APPROVED PLANS FOR THE COMMERCIAL RENOVATION PROJECT |
| | UNDER PERMIT 20010838, HOWEVER I AM NOT ABLE TO LOCATE |
| | A PERMIT FOR THE RANGE OR A PERMIT FOR ANY OTHER GAS |
| | PIPING. PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | THE RANGE- SECTION 623.1 FBC FG. |
| | |
| | 4) CLARIFY IF THE GAS RANGE IS THE ONLY GAS-FIRED |
| | APPLIANCE BEING SERVED BY THE EXISTING METER. IF THERE |
| | ARE OTHER GAS-FIRED EQUIPMENT OR APPLIANCES BEING |
| | SERVED BY THE METER, THEN THE ISOMETRIC DRAWING MUST BE |
| | MODIFIED TO SHOW THE ENTIRE GAS PIPING SYSTEM INCLUDING |
| | THE LONGEST RUN LENGTH AND BRANCH PIPING LENGTHS, |
| | INDIVIDUAL AND TOTAL BTUH LOADS OF APPLIANCES OR |
| | EQUIPMENT, TYPES AND SIZES OF PIPING, LOCATIONS OF |
| | REGULATORS AND SHUTOFF VALVES- SECTION 401.4 FBC FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |