| 2020-09-08 09:28:30 | 09/08/20 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE COOK TO NEED TO BE FULL LOAD, IT IS LABELED AT |
| | 18 BTU'S AND THERE IS 6 BURNERS AND A GRILL EACH AT 18 |
| | X 7 EQUALS 126 BTU'S PLEASE CHANGE AND RECALCULATE FOR |
| | SIZING IF NEEDED PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| | PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. PLEASE LABEL THE TYPE OF PIPE MATERIAL BEING |
| | INSTALLED AND THE CORRESPONDING EHD NUMBER OF THE |
| | CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR |
| | EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. PLEASE LABEL THE TYPE OF GAS (LP OR NATURAL) PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 5. THIS TANKLESS UNIT CALL FOR 10.5" WATER COLUMN AND |
| | THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN |
| | REQUIRING A REGULATOR FOR THIS UNIT AS PER |
| | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. |
| | SEC. G2421.1. |
| | |
| | 6. POOL HEATER IS MISSED LABELED AT 440 BTU'S AND SPECS |
| | SAYS 400 BTU'S PLEASE CORRECT PER THE WPB AMENDMENTS TO |
| | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 7. SUBMIT COMBUSTION AIR CALCULATIONS FOR (DRYER SHOW |
| | LOCATION, IF IN CLOSET ARE LOUVER BEING USED, AND |
| | RANGE) GAS APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED |
| | BY THE BUILDING'S MECHANICAL VENTILATION SYSTEM, THE |
| | SYSTEM SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE |
| | IN ADDITION TO THE REQUIRED VENTILATION AIR PER THE |
| | 2017 FBC RES. SEC. G2407.9.3. COMBINED COMBUSTION AIR |
| | AND VENTILATION AIR SYSTEM. |
| | |
| | 8. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC RES. SEC. G2413.2. |
| | |
| | 9. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 10. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| | TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING |
| | DETAILS OF THE GAS VENT(S) FOR THE TANKLESS HEATER |
| | INSIDE PER THE 2017 FBC RES. SECS. G2426 THRU G2429.1. |
| | |
| | 11. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER |
| | A ROOF PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | 12. IF THE GAS GRILL IS IN A COVERED PATIO, AND A HOOD |
| | IS REQUIRED A SEPARATE PERMIT FOR THE HOOD IS REQUIRED |
| | PLEASE NOT ON PLANS PER THE 2017 FBC RES. SEC. G2408.1. |
| | |
| | 13. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF |
| | REGULATOR 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC |
| | G2421.2. |
| | |
| | 14. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER |
| | THE 2017 FBC RES. SEC. G2401.1.3. |
| | |
| | 15. SHOW AND LABEL DRIP LEG ON EQUIPMENT INSTALLED, |
| | EXCEPT FOR APPLIANCES, RANGE, DRYERS & OD GRILLS PER |
| | THE 2017 FBC RES. SEC. G2419.2 OR 2017 FBC FG 408.2. |
| | |
| | 16. SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS FOR |
| | THE GAS DRYER. THE GAS DRYER SHALL BE LISTED AND |
| | LABELED PER THE 2017 FBC FG RES. SEC. G2404.3. THE |
| | MANUFACTURER'S SPECIFICATIONS SHALL NOTE THE CFM'S THAT |
| | ARE BEING EXHAUSTED BY THE DRYER. |
| | |
| | 17. ON THE HOUSE PLAN SHOW THE LOCATION OF THE TANKLESS |
| | WATER HEATER AND THE LOCATION AND DISTANCE OF ANY |
| | OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| | HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY |
| | WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE |
| | HOUSE PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |