2020-09-15 17:18:171ST REVIEW FBC-2017 RES.
 PERMIT- 20090143
 9/15/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER DRAWING:
 A) PROVIDE THE TOTAL LENGTH OF THE INTERIOR PIPING RUN
 AND THE TOTAL DEVELOPED LENGTH OF THE ENTIRE SYSTEM-
 SECTIONS G2413.4.1 AND G2413.4.2 FBC RES.
 B) PROVIDE THE BTUH LOAD OF THE GENERATOR AND THE TOTAL
 BTUH LOAD OF THE SYSTEM, INTERIOR APPLIANCES AND NEW
 GENERATOR COMBINED- SECTIONS G2412.3, G2412.4, &
 G2413.2 FBC RES. A) INDICATE THE TYPES, LENGTHS, AND
 SIZES OF THE MAIN PIPE FROM THE METER, THE BRANCH PIPE
 INTO THE HOUSE, AND THE BRANCH DROPPING INTO THE
 UNDERGROUND PE- SECTIONS G2413.4.1 & G2413.4.2.
 C) PROVIDE THE PIPE SIZING TABLES FOR THE MAIN AND
 BRANCH LINES FROM THE METER, AND THE PE. PLEASE NOTE
 THE SUBMITTED COPY OF TABLE 402.4(32) IS FOR LP GAS-
 THIS IS A NAT. GAS SYSTEM. REFER TO TABLES G2413.4(1)
 THROUGH G2413.4(8) FBC RES. RELATIVE SIZING TABLES FROM
 THE FBC FG MAY BE SUBSTITUTED.
 D) THE REDUCED (11 IN. W.C.) OUTLET PRESSURE AT THE
 REGULATOR FOR THE GENERATOR IS INCORRECT. THE REQUIRED
 INLET PRESSURE AT THE GENERATOR PER THE SUBMITTED SPECS
 IS (3.5- 7 IN. W.C.) FOR NAT. GAS- PLEASE CORRECT.
 E) INDICATE ON THE RISER WHICH B42 REGULATOR MODELS
 WILL BE INSTALLED- MODEL R, N, OR H AND SUBMIT
 HIGHLIGHTED OR MARKED UP SPEC SHEETS SHOWING THE MAX
 INLET AND OUTLET SIZE AND PRESSURES, SPRING DATA,
 SPRING COLOR OUTLET PRESSURE RANGE AND ORIFICE SIZE-
 SECTION G2421.1 & G2421.2 FBC RES.
 E) PLEASE IDENTIFY THE SHUTOFF VALVE FOR THE GAS SUPPLY
 TO THE GENERATOR, AND THE REQUIRED PIPE UNIONS AT THE
 REGULATORS- SECTIONS G2420.4, G2420.5, AND G2421.2(7).
 THE DRAWING APPEARS TO BE USING THE SAME X SYMBOL FOR
 REGULATORS AND VALVES AT THE GENERATOR AND THE METER.
 F) SUBMIT MANUFACTURER'S SPECS FOR THE GENERATOR FLEX
 CONNECTOR THAT INDICATE MANUFACTURER AND MODEL, LISTING
 STANDARDS, AND INSTALLATION GUIDELINES- SECTION
 G2415.1.
 G) INDICATE A TRACER WIRE WILL BE INSTALLED ADJACENT TO
 THE UG PE PIPING- SECTION G2415.17.3
 H) INDICATE HOW THE PE PIPING RISER WILL CONNECT TO THE
 FLEX CONNECTOR AND TO THE SCHEDULE 40 METALLIC PIPE PER
 SECTIONS G2415.17.1 & G2415.17.2. PLEASE NOTE THAT
 SPECS FOR ANODELESS RISERS AND PE/METALLIC PIPE
 CONNECTORS SHALL BE LISTED AND LABELED.
 I) SHOW THE LOCATION OF THE DRIP LEG- SECTION G2419.2
 FBC RES.
  
 2) PLEASE SUBMIT INSTALLATION GUIDELINES FROM GENERAC
 TO VERIFY THE LOCATION CLEARANCES FOR THE GENERATOR AS
 SHOWN ON THE PLAN AND SURVEY ARE CONSISTENT WITH THE
 MANUFACTURER'S SPECIFICATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  