| Date |
Text |
| 2020-09-15 17:18:17 | 1ST REVIEW FBC-2017 RES. |
| | PERMIT- 20090143 |
| | 9/15/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER DRAWING: |
| | A) PROVIDE THE TOTAL LENGTH OF THE INTERIOR PIPING RUN |
| | AND THE TOTAL DEVELOPED LENGTH OF THE ENTIRE SYSTEM- |
| | SECTIONS G2413.4.1 AND G2413.4.2 FBC RES. |
| | B) PROVIDE THE BTUH LOAD OF THE GENERATOR AND THE TOTAL |
| | BTUH LOAD OF THE SYSTEM, INTERIOR APPLIANCES AND NEW |
| | GENERATOR COMBINED- SECTIONS G2412.3, G2412.4, & |
| | G2413.2 FBC RES. A) INDICATE THE TYPES, LENGTHS, AND |
| | SIZES OF THE MAIN PIPE FROM THE METER, THE BRANCH PIPE |
| | INTO THE HOUSE, AND THE BRANCH DROPPING INTO THE |
| | UNDERGROUND PE- SECTIONS G2413.4.1 & G2413.4.2. |
| | C) PROVIDE THE PIPE SIZING TABLES FOR THE MAIN AND |
| | BRANCH LINES FROM THE METER, AND THE PE. PLEASE NOTE |
| | THE SUBMITTED COPY OF TABLE 402.4(32) IS FOR LP GAS- |
| | THIS IS A NAT. GAS SYSTEM. REFER TO TABLES G2413.4(1) |
| | THROUGH G2413.4(8) FBC RES. RELATIVE SIZING TABLES FROM |
| | THE FBC FG MAY BE SUBSTITUTED. |
| | D) THE REDUCED (11 IN. W.C.) OUTLET PRESSURE AT THE |
| | REGULATOR FOR THE GENERATOR IS INCORRECT. THE REQUIRED |
| | INLET PRESSURE AT THE GENERATOR PER THE SUBMITTED SPECS |
| | IS (3.5- 7 IN. W.C.) FOR NAT. GAS- PLEASE CORRECT. |
| | E) INDICATE ON THE RISER WHICH B42 REGULATOR MODELS |
| | WILL BE INSTALLED- MODEL R, N, OR H AND SUBMIT |
| | HIGHLIGHTED OR MARKED UP SPEC SHEETS SHOWING THE MAX |
| | INLET AND OUTLET SIZE AND PRESSURES, SPRING DATA, |
| | SPRING COLOR OUTLET PRESSURE RANGE AND ORIFICE SIZE- |
| | SECTION G2421.1 & G2421.2 FBC RES. |
| | E) PLEASE IDENTIFY THE SHUTOFF VALVE FOR THE GAS SUPPLY |
| | TO THE GENERATOR, AND THE REQUIRED PIPE UNIONS AT THE |
| | REGULATORS- SECTIONS G2420.4, G2420.5, AND G2421.2(7). |
| | THE DRAWING APPEARS TO BE USING THE SAME X SYMBOL FOR |
| | REGULATORS AND VALVES AT THE GENERATOR AND THE METER. |
| | F) SUBMIT MANUFACTURER'S SPECS FOR THE GENERATOR FLEX |
| | CONNECTOR THAT INDICATE MANUFACTURER AND MODEL, LISTING |
| | STANDARDS, AND INSTALLATION GUIDELINES- SECTION |
| | G2415.1. |
| | G) INDICATE A TRACER WIRE WILL BE INSTALLED ADJACENT TO |
| | THE UG PE PIPING- SECTION G2415.17.3 |
| | H) INDICATE HOW THE PE PIPING RISER WILL CONNECT TO THE |
| | FLEX CONNECTOR AND TO THE SCHEDULE 40 METALLIC PIPE PER |
| | SECTIONS G2415.17.1 & G2415.17.2. PLEASE NOTE THAT |
| | SPECS FOR ANODELESS RISERS AND PE/METALLIC PIPE |
| | CONNECTORS SHALL BE LISTED AND LABELED. |
| | I) SHOW THE LOCATION OF THE DRIP LEG- SECTION G2419.2 |
| | FBC RES. |
| | |
| | 2) PLEASE SUBMIT INSTALLATION GUIDELINES FROM GENERAC |
| | TO VERIFY THE LOCATION CLEARANCES FOR THE GENERATOR AS |
| | SHOWN ON THE PLAN AND SURVEY ARE CONSISTENT WITH THE |
| | MANUFACTURER'S SPECIFICATIONS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |