Plan Review Notes
Plan Review Notes For Permit 20090143
Permit Number 20090143
Review Stop B
Sequence Number 1
Notes
Date Text
2020-09-24 16:45:34PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW ON THE SURVEY/SITE PLAN THAT THE GENERATOR
 EXHAUST IS LOCATED A MINIMUM OF 10' FROM ANY OPENINGS
 INTO THE BUILDING. FBC M501.3
  
 THE HONEYWELL GENERATOR IS NOT LISTED ON THE PREFAB
 GENERATOR PAD ENGINEERING, HOWEVER, ITS DIMENSIONS AND
 WEIGHT MATCH THE REQUIREMENTS OF THE PAD AND WINDLOADS.
 THIS IS ACCEPTABLE.
  
  
  
  
  
2020-09-08 14:03:45VALUE APPEARS LOW. CT