| 2020-09-24 16:45:34 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SHOW ON THE SURVEY/SITE PLAN THAT THE GENERATOR | | | EXHAUST IS LOCATED A MINIMUM OF 10' FROM ANY OPENINGS | | | INTO THE BUILDING. FBC M501.3 | | | | | | THE HONEYWELL GENERATOR IS NOT LISTED ON THE PREFAB | | | GENERATOR PAD ENGINEERING, HOWEVER, ITS DIMENSIONS AND | | | WEIGHT MATCH THE REQUIREMENTS OF THE PAD AND WINDLOADS. | | | THIS IS ACCEPTABLE. | | | | | | | | | | | | | | | | | 2020-09-08 14:03:45 | VALUE APPEARS LOW. CT |
|