| 2020-09-17 15:19:00 | 09/17/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE STATE THE OCCUPANCY TYPE AND AS TO WHY THERE |
| | IS ONLY ONE ACCESSIBLE TOILET RESTROOM, SO PLEASE SITE |
| | THE APPLICABLE CODE SECTION THAT ALLOWS ONLY ONE. |
| | |
| | 2. ON THE SHEETS ADA 1.0 AND 1.1 PLEASE DELETE WATER |
| | FOUNTAIN AND ANY OTHER PLUMBING DETAILS THAT DO NOT |
| | PURITAN TO THIS PROJECT PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. ON THE SHEET, A-3 THE LAUNDRY ROOM SHOWS THREE |
| | WASHING MACHINES AND ON ISOMETRIC, THERE ARE TWO SHOWN |
| | PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. THE LAUNDRY ROOM REQUIRES A LINT TRAP PER THE 2017 |
| | FBC SEC. P 1003.6, PLEASE PROVIDE SPECIFICATION AND OR |
| | DETAIL ON PLANS. |
| | |
| | 5. PLEASE SHOW THE LOCATION OF LAUNDRY VALVES THAT |
| | SHALL ACCESSIBLE WITHOUT MOVING UNITS PER THE 2017 FBC |
| | SEC. 606.3 ACCESS TO VALVES. |
| | |
| | 6. ON THE SHEET, P 3.1 PLEASE PROVIDE A WATER RISER FOR |
| | THE LAUNDRY ROOM ON ISOMETRIC RISER PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. PLEASE NOTE THAT IS USING A |
| | COMMERCIAL MACHINE THEY MAY REQUIRE A 3/4" INCH SUPPLY |
| | PER MANUFACTURE SPECIFICATION. |
| | |
| | 7. ON SHEET A-3 PLEASE GIVE THE DIMENSION'S ACCESSIBLE |
| | CLEAR FLOOR SPACE FOR THE LAUNDRY ROOM PER THE 2017 FBC |
| | ACC SEC. 611. |
| | |
| | 8. ON THE SHEET, A-3 DETAIL 2/A-3 THE SHOWER GRAB BARS |
| | SHALL BE 36" TO TOP OF THE BAR PER THE 2017 ACC SEC. |
| | 609.4. |
| | |
| | 9. ON THE SHEET, A-3 PLEASE SHOW THE HEIGHT OF THE |
| | SPRAY UNIT PER THE 2017 FBC ACC. SEC. 608.6. |
| | |
| | 10. ON THE SHEET, A-3 PLEASE SHOW FLOOR SPACE FOR |
| | SHOWER AND GIVE DEMISSION FOR ALL CLEAR FLOOR SPACE ON |
| | ALL ACCESSIBILITY PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 11. ON THE SHEET, P 3.1 THE ISOMETRIC FOR THE DISCHARGE |
| | OF THE WASHING MACHINE SHOWS A DOUBLE SANITARY TEE |
| | PATTERN THIS IS NOT ALLOWED PER THE 2017 FBC SEC. |
| | 706.3. |
| | |
| | 12. ON SHEET P 3.1 FOR P-2 RISER IS PRESENT ANT IT |
| | REPRESENTS N-143 AND N-171 BUT THESE BATHROOM GROUPS |
| | ARE MISSING THE LAVS AND SHOWER WATER AND SANITARY |
| | RISER DIAGRAMS PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 13. ON THE SHEET, A1.1 FOR ACCESSIBLE CLEAR FLOOR SPACE |
| | OF THE SHOWER IS MISSING PLEASE SHOW ON ALL PAGES ( |
| | A1.2, A 2.1 AND A2.2 ) PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 14. ON THE SHEET, P 3.1 PLEASE REFER TABLE 906.1 ON THE |
| | VENT FOR P-3 AND RECALCULATE TOTAL FIXTURE UNITS FOR 2" |
| | VENT AS IT MAY NEED TO BE INCREASED IF A THIRD WASHING |
| | MACHINE IS ADDED PER 2017 FBC SEC. P 906. |
| | |
| | 15. ON THE SHEET, P 3.1 FOR EVERY TIME THAT WATER GOES |
| | INTO A UNIT FROM A WATER RISER WITH A VALVE THAT IS |
| | ACCESSIBLE SHALL BE FULLY OPEN PER THE 2017 FBC SEC. P |
| | 606.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |