| 2020-09-14 10:45:48 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20090118 |
| | ADD: 4847 DAVID S MACK DR. |
| | CONT: IBIS BUILDING CORP. |
| | TEL: 561-568-2570 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SEPT. 14TH/2020 |
| | ACTION: DENIED |
| | |
| | 1) THE LIFE SAFETY SHEET 1 & 2 FOR FLOORS 1, 2, 3 & 4 |
| | THE DOUBLE DOORS FROM SMOKE COMPARTMENT M AND THE |
| | NURSES CENTRAL STATION AND CENTRAL BATHING STATION ARE |
| | IN CONFLICT WITH EACH OTHER. ON ALL 4 FLOORS THE |
| | CENTRAL BATHING STATION SHOWS A DOUBLE ACTING PIVOT |
| | DOOR THAT SWINGS INTO THE SMOKE COMPARTMENT EGRESS |
| | DOORS. PLEASE REVIEW THE 017 FBC-B SECTION 1005.7.1. |
| | DOORS, WHEN FULLY OPEN, SHALL NOT REDUCE THE REQUIRED |
| | WIDTH BY MORE THAN 7 INCHES. DOORS IN ANY POSITION |
| | SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE THAN |
| | ONE-HALF. |
| | 2) SHEET A4 SHOWS IN ALL THE CENTRAL BATHING FACILITIES |
| | GYPSUM WALL BOARD AND EPOXY PAINT. PLEASE REVIEW 2017 |
| | FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT IS A |
| | RESULT OF THE BUILDING OFFICIAL INTERPRETATION. IN |
| | RESTROOMS EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH |
| | HARD, NON-ABSORBENT SURFACE. WALLS & PARTITIONS WITHIN |
| | 2 FEET OF SERVICE SINKS, URINALS, AND WATER CLOSETS |
| | SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT SURFACE TO A |
| | HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT |
| | FOR STRUCTURAL ELEMENTS, THE MATERIAL USED IN SUCH |
| | WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED |
| | BY MOISTURE. |
| | |
| | |
| | 2B) 2017 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS |
| | A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS |
| | AND CEILING PANELS IN SHOWER AREAS SHALL BE OF |
| | MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN |
| | ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER |
| | RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE |
| | FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN |
| | INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND |
| | THE MANUFACTURE?S RECOMMENDATIONS. |
| | |
| | 2C) 2017 FBC-B SHOWERS & TUBS 1210.3. SHOWER |
| | COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS |
| | SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A |
| | HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET. |
| | |
| | 2D) SHEET A5 DETAIL P-3 INDICATES WITH A NOTE THAT THE |
| | SHOWER WATERPROOFING BUILDING PANEL SYSTEM PER |
| | MANUFACTURERS RECOMMENDATIONS. NO PRODUCT INFORMATION |
| | WAS SUBMITTED THIS REVIEW. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |