| | 1ST REVIEW |
| | DATE: MON. SEPT. 14TH/2020 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1A SHEET FP1.05 SHOWS THE REMOVAL OF FIRE SPRINKLERS |
| | FROM THE IT ROOM. THIS TYPE OF ROOMS IS 1-HOUR FIRE |
| | RATES, THE PLANS DO NOT PROVIDE THE THROUGH |
| | -PENETRATION FIRESTOP SYSTEM FOR THE WHOLE WHEN THE 2 ? |
| | INCH SPRINKLER PIPE IS REMOVED. 2017 FBC-B SECTION |
| | 714.3.1.2. |
| | |
| | 1B) IF WALL SECTIONS ARE TO BE REMOVED THEN THE NEW |
| | WALL SECTIONS MUST MEET THE REQUIREMENTS OF 2017 FBC-B |
| | 715.2 S FIRE-RESISTANT JOINT SYSTEM SHALL BE SECURELY |
| | INSTALLED IN ACCORDANCE WITH THE LISTING CRITERIA IN OR |
| | ON THE JOINT FOR ITS ENTIRE LENGTH SO AS NOT TO |
| | DISLODGE, LOOSEN OR OTHERWISE IMPAIR ITS ABILITY TO |
| | ACCOMMODATE MOVEMENTS AND TO RESIST THE PASSAGE OF FIRE |
| | AND HOT GASES. |
| | |