2020-11-16 14:00:12WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090083
 ADD: 301 SOUTHERN BLVD.
 CONT: TBD/ TO BE ANNOUNCED
 TEL: ???
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. NOV. 16TH/ 2020
 ACTION: DENIED
  
 1-2) COMPLIED
  
 3A) COMPLIED.
  
 3B) SEMI-COMPLIED/ 2ND REQUEST. SHEET A1.3 THE NEW
 DETAIL 3 DOES SHOW A DOUBLE LINE DETAIL BUT NOT
 CONFORMANCE WITH . WEST PALM MUNI-CODE ARTICLE XV
 PARKING DETAIL, 94-485 ILLUSTRATES WITH MEASUREMENTS
 FOR DOUBLE STRIPE STALL PAINTING. MISSING THE THICKNESS
 OF THE PAINTED LINES AND THE DISTANCE BETWEEN THE
 DOUBLE PAINTED LINES.
  
 1ST ROUND OF COMMENTS. THE SITE PLAN SHOWS THE PARKING
 SPACES WITH A SINGLE LINE. ACCESSIBLE PARKING SPACE /
 STALL PAINTING. 2017 ACCESSIBILITY CODE SECTION 502.2
 VEHICLE SPACES. EACH PARKING SPACE MUST BE AT LEAST 12
 FEET WIDE, SHALL BE MARKED TO DEFINE THE WIDTH, AND
 SHALL HAVE AN ADJACENT ACCESS AISLE COMPLYING WITH
 502.3.
 ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR
 OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT
 MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485
 ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL
 PAINTING.
  
  
 4A) BUILDING PROVISO: DUMPSTER ENCLOSURE TO BE
 SUBMITTED UNDER SEPARATE PERMIT.
 SHEET A1.4. DUMPSTER DO TAKE A SEPARATE PERMIT REVIEW
 AND ASSOCIATED FEES. DETAIL # 3 STATES FOOTING DETAIL
 AND CMU WALL BOTH REFER TO STRUCTURAL SHEETS. SUBMIT
 THE STRUCTURAL SHEET WITH DETAILS FOR REVIEW.
  
 4B) BUILDING PROVISO / TO BE REVIEWED BY ENGINEERING/
 PUBLIC WORKS.
  
 4C) NOTED, NO ACTION REQUIRED. OTHER PERMITS THAT ARE
 NOT INCLUDED IN THIS REVIEW ARE FIRE SPRINKLER, FIRE
 ALARM, RACK STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR
 ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK
 IN COOLERS & FREEZERS, ALL LOW VOLTAGE PERMITS,
 GENERATORS & FUEL TANKS, GAS PERMIT, POOL, JACUZZI AND
 ASSOCIATED SUB-PERMITS, AWNING, SCREEN ENCLOSURES,
 CANOPY, FENCE, LANDSCAPE, IRRIGATION, AUGER CAST PILE
 AND OR FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE
 SEPARATE REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
  
 5-6) COMPLIED.
  
 7)BUILDING PROVISO: SHEET S102 SHOWS NEW OPEN WEB STEEL
 JOIST, DECK AND NEW C15X 33.9 STEEL BEAMS. WELDED OR
 BOLTED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED. REPORTS SUBMITTED TO
 BUILDING INSPECTOR AT TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 8) COMPLIED.
  
 9) NOTICE ONLY, NO ACTION NEEDS TO BE TAKEN. SHEET S001
 INDICATES THE WALL AND ROOF PRESSURES IN VASD, THEY ARE
 GOOD!!!!
  
 10-13 DEFERRED SUBMITTALS/ BUILDING PROVISO: THE SHEET
 A-01 INDICATES DEFERRED SUBMITTAL INDICATES SEE SHEET
 A6.0 FOR PRODUCT APPROVALS. A FULL LIST OF REQUIRED
 PRODUCT APPROVALS FOR COMPONENTS AND CLADDING SEE
 BELOW:
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS
 SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS, CURBS
 (G) PRE-ENGINEERED A/C STANDS
  
 11)BUILDING PROVISO: W. P. B. 107.3.4. PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY
 FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 12)BUILDING PROVISO: DEFERRED SUBMITTALS AS REQUESTED
 ON SHEET A-01. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 13) BUILDING PROVISO: IDENTIFY GLAZING/ MULLIONS.
 PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 14) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved