| Date |
Text |
| 2020-11-16 14:00:12 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20090083 |
| | ADD: 301 SOUTHERN BLVD. |
| | CONT: TBD/ TO BE ANNOUNCED |
| | TEL: ??? |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. NOV. 16TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1-2) COMPLIED |
| | |
| | 3A) COMPLIED. |
| | |
| | 3B) SEMI-COMPLIED/ 2ND REQUEST. SHEET A1.3 THE NEW |
| | DETAIL 3 DOES SHOW A DOUBLE LINE DETAIL BUT NOT |
| | CONFORMANCE WITH . WEST PALM MUNI-CODE ARTICLE XV |
| | PARKING DETAIL, 94-485 ILLUSTRATES WITH MEASUREMENTS |
| | FOR DOUBLE STRIPE STALL PAINTING. MISSING THE THICKNESS |
| | OF THE PAINTED LINES AND THE DISTANCE BETWEEN THE |
| | DOUBLE PAINTED LINES. |
| | |
| | 1ST ROUND OF COMMENTS. THE SITE PLAN SHOWS THE PARKING |
| | SPACES WITH A SINGLE LINE. ACCESSIBLE PARKING SPACE / |
| | STALL PAINTING. 2017 ACCESSIBILITY CODE SECTION 502.2 |
| | VEHICLE SPACES. EACH PARKING SPACE MUST BE AT LEAST 12 |
| | FEET WIDE, SHALL BE MARKED TO DEFINE THE WIDTH, AND |
| | SHALL HAVE AN ADJACENT ACCESS AISLE COMPLYING WITH |
| | 502.3. |
| | ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR |
| | OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT |
| | MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. |
| | WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485 |
| | ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL |
| | PAINTING. |
| | |
| | |
| | 4A) BUILDING PROVISO: DUMPSTER ENCLOSURE TO BE |
| | SUBMITTED UNDER SEPARATE PERMIT. |
| | SHEET A1.4. DUMPSTER DO TAKE A SEPARATE PERMIT REVIEW |
| | AND ASSOCIATED FEES. DETAIL # 3 STATES FOOTING DETAIL |
| | AND CMU WALL BOTH REFER TO STRUCTURAL SHEETS. SUBMIT |
| | THE STRUCTURAL SHEET WITH DETAILS FOR REVIEW. |
| | |
| | 4B) BUILDING PROVISO / TO BE REVIEWED BY ENGINEERING/ |
| | PUBLIC WORKS. |
| | |
| | 4C) NOTED, NO ACTION REQUIRED. OTHER PERMITS THAT ARE |
| | NOT INCLUDED IN THIS REVIEW ARE FIRE SPRINKLER, FIRE |
| | ALARM, RACK STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR |
| | ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK |
| | IN COOLERS & FREEZERS, ALL LOW VOLTAGE PERMITS, |
| | GENERATORS & FUEL TANKS, GAS PERMIT, POOL, JACUZZI AND |
| | ASSOCIATED SUB-PERMITS, AWNING, SCREEN ENCLOSURES, |
| | CANOPY, FENCE, LANDSCAPE, IRRIGATION, AUGER CAST PILE |
| | AND OR FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE |
| | SEPARATE REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | |
| | 5-6) COMPLIED. |
| | |
| | 7)BUILDING PROVISO: SHEET S102 SHOWS NEW OPEN WEB STEEL |
| | JOIST, DECK AND NEW C15X 33.9 STEEL BEAMS. WELDED OR |
| | BOLTED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO |
| | PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR |
| | PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH |
| | THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR |
| | FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY |
| | CERTIFICATION WILL BE REQUIRED. REPORTS SUBMITTED TO |
| | BUILDING INSPECTOR AT TIME OF FRAMING INSPECTION. |
| | 2017 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT |
| | 561-805-6666. |
| | |
| | 8) COMPLIED. |
| | |
| | 9) NOTICE ONLY, NO ACTION NEEDS TO BE TAKEN. SHEET S001 |
| | INDICATES THE WALL AND ROOF PRESSURES IN VASD, THEY ARE |
| | GOOD!!!! |
| | |
| | 10-13 DEFERRED SUBMITTALS/ BUILDING PROVISO: THE SHEET |
| | A-01 INDICATES DEFERRED SUBMITTAL INDICATES SEE SHEET |
| | A6.0 FOR PRODUCT APPROVALS. A FULL LIST OF REQUIRED |
| | PRODUCT APPROVALS FOR COMPONENTS AND CLADDING SEE |
| | BELOW: |
| | 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS, MULLIONS. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS |
| | SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| | CONCRETE INSULATION, ROOF TOP VENTILATORS, CURBS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 11)BUILDING PROVISO: W. P. B. 107.3.4. PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY |
| | FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 12)BUILDING PROVISO: DEFERRED SUBMITTALS AS REQUESTED |
| | ON SHEET A-01. 107.3.4.2 DEFERRED SUBMITTALS. FOR THE |
| | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 13) BUILDING PROVISO: IDENTIFY GLAZING/ MULLIONS. |
| | PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| | SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| | TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| | TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| | OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 14) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |