| 2020-09-17 14:08:25 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. PER WPB FBC 107.2.1, IDENTIFY EXISTING EMERGENCY |
| | OVERFLOW SCUPPERS OR PROVIDE NEW TO COMPLY WITH FBC PL |
| | 1108.1. PROVIDE DETAIL OF SAME. |
| | |
| | 2. RE: S-1 HAND SINK; FIXTURE SHALL BE SEPARATELY |
| | TRAPPED BY A LIQUID SEAL TRAP AND DIRECTLY CONNECTED TO |
| | THE DRAINAGE SYSTEM IN ACCORDANCE WITH FBC PL CHAPTER 7 |
| | PER FBC PL 802.1 AND 1002.1. FIXTURE TRAP SHALL BE |
| | VENTED IN ACCORDANCE WITH FBC PL CHAPTER 9, WHICH |
| | INCLUDES THE USE OF AIR ADMITTANCE VALVES AS NOTED IN |
| | SECTION 918. |
| | |
| | 3. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR TRAP PRIMER, |
| | SHOW ON WATER RISER DIAGRAM, WATER CONNECTION TO SIOUX |
| | CHIEF #695 TRAP PRIMER VALVE(S) AND ON SANITARY RISER |
| | DIAGRAM TRAP PRIMER CONNECTIONS TO REQUIRED TRAPS. |
| | |
| | 4. RE: EF1.1; PER WPB FBC 107.2.1, SHOW LOCATION AND |
| | PROVIDE DETAIL ON PLUMBING PLAN FOR ITEM 22, MCCANN |
| | WATER BOOSTER AND A MANUFACTURER?S |
| | SPECIFICATION/INSTALLATION MANUAL. IS THIS FOR A |
| | CARBONATED BEVERAGE DISPENSER. I CANNOT FIND ANY SUCH |
| | DISPENSER ON THE PLANS OR SCHEDULE. PLEASE CLARIFY. |
| | WATER SUPPLY SYSTEM SHALL BE PROTECTED BY A BACKFLOW |
| | PREVENTION DEVICE COMPLYING WITH FBC PL 608.16.1. |
| | |
| | 5. PER WPB FBC 107.2.1, INDICATE ON THE PLUMBING PLAN |
| | THE FIXTURES THAT ARE TO BE PROVIDED WITH THE TMV NOTED |
| | ON P1.0, SPECIALTY FIXTURE SCHEDULE AND PROVIDE NOTE |
| | STATING TMV IS ASSE 1070 COMPLIANT. |
| | |
| | 6. PER WPB FBC 107.2.1, PROVIDE UP TO DATE |
| | CERTIFICATION OF THE EXISTING BACKFLOW PREVENTER NOTED |
| | ON P1.1. |
| | |
| | 7. RE: P1.1 AND P2.0: PER WPB FBC 107.2.1, TO BE CLEAR, |
| | PROVIDE SIZE OF EXPANSION TANK TO BE INSTALLED WITH THE |
| | SPECIFIED WATER HEATER. |
| | |
| | 8. RE: P1.1 AND P2.0: PER WPB FBC 107.2.1, PROVIDE |
| | DETAIL FOR WATER HEATER SHELF SPECIFYING MEANS, METHOD, |
| | MATERIALS, ANCHORS AND IF APPLICABLE, WATER HEATER |
| | RESTRAINTS. |
| | |
| | 9. PER FBC PL 606.1(5), FULL OPEN VALVES SHALL BE |
| | INSTALLED AT TOP OF EVERY WATER DOWN FEED PIPE. |
| | |
| | 10. PER FBC PL 606.1(8), THE BALL VALVE IN WATER SUPPLY |
| | TO THE WATER HEATER SHALL BE FULL PORT. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20090083 301 SOUTHERN BLVD |
| | |
| | |