Plan Review Notes
Plan Review Notes For Permit 20090083
Permit Number 20090083
Review Stop P
Sequence Number 1
Notes
Date Text
2020-09-17 14:08:25CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. PER WPB FBC 107.2.1, IDENTIFY EXISTING EMERGENCY
 OVERFLOW SCUPPERS OR PROVIDE NEW TO COMPLY WITH FBC PL
 1108.1. PROVIDE DETAIL OF SAME.
  
 2. RE: S-1 HAND SINK; FIXTURE SHALL BE SEPARATELY
 TRAPPED BY A LIQUID SEAL TRAP AND DIRECTLY CONNECTED TO
 THE DRAINAGE SYSTEM IN ACCORDANCE WITH FBC PL CHAPTER 7
 PER FBC PL 802.1 AND 1002.1. FIXTURE TRAP SHALL BE
 VENTED IN ACCORDANCE WITH FBC PL CHAPTER 9, WHICH
 INCLUDES THE USE OF AIR ADMITTANCE VALVES AS NOTED IN
 SECTION 918.
  
 3. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR TRAP PRIMER,
 SHOW ON WATER RISER DIAGRAM, WATER CONNECTION TO SIOUX
 CHIEF #695 TRAP PRIMER VALVE(S) AND ON SANITARY RISER
 DIAGRAM TRAP PRIMER CONNECTIONS TO REQUIRED TRAPS.
  
 4. RE: EF1.1; PER WPB FBC 107.2.1, SHOW LOCATION AND
 PROVIDE DETAIL ON PLUMBING PLAN FOR ITEM 22, MCCANN
 WATER BOOSTER AND A MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL. IS THIS FOR A
 CARBONATED BEVERAGE DISPENSER. I CANNOT FIND ANY SUCH
 DISPENSER ON THE PLANS OR SCHEDULE. PLEASE CLARIFY.
 WATER SUPPLY SYSTEM SHALL BE PROTECTED BY A BACKFLOW
 PREVENTION DEVICE COMPLYING WITH FBC PL 608.16.1.
  
 5. PER WPB FBC 107.2.1, INDICATE ON THE PLUMBING PLAN
 THE FIXTURES THAT ARE TO BE PROVIDED WITH THE TMV NOTED
 ON P1.0, SPECIALTY FIXTURE SCHEDULE AND PROVIDE NOTE
 STATING TMV IS ASSE 1070 COMPLIANT.
  
 6. PER WPB FBC 107.2.1, PROVIDE UP TO DATE
 CERTIFICATION OF THE EXISTING BACKFLOW PREVENTER NOTED
 ON P1.1.
  
 7. RE: P1.1 AND P2.0: PER WPB FBC 107.2.1, TO BE CLEAR,
 PROVIDE SIZE OF EXPANSION TANK TO BE INSTALLED WITH THE
 SPECIFIED WATER HEATER.
  
 8. RE: P1.1 AND P2.0: PER WPB FBC 107.2.1, PROVIDE
 DETAIL FOR WATER HEATER SHELF SPECIFYING MEANS, METHOD,
 MATERIALS, ANCHORS AND IF APPLICABLE, WATER HEATER
 RESTRAINTS.
  
 9. PER FBC PL 606.1(5), FULL OPEN VALVES SHALL BE
 INSTALLED AT TOP OF EVERY WATER DOWN FEED PIPE.
  
 10. PER FBC PL 606.1(8), THE BALL VALVE IN WATER SUPPLY
 TO THE WATER HEATER SHALL BE FULL PORT.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20090083 301 SOUTHERN BLVD
  
  