| Date |
Text |
| 2020-09-21 13:19:09 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 1.5 - A BASEMENT WITH STORAGE ROOMS IS |
| | INDICATED. |
| | |
| | THERE ARE NO DIMENSIONS NOR SQ FT INDICATED. |
| | |
| | PER NFPA 1, CH 13 |
| | |
| | 13.3.2.2 BASEMENTS EXCEEDING 2500 FT2 (232 M2) IN NEW |
| | BUILDINGS |
| | SHALL BE PROTECTED THROUGHOUT BY AN APPROVED AUTOMATIC |
| | SPRINKLER |
| | SYSTEM. |
| | |
| | PLEASE PROVIDE |
| | |
| | |
| | 2) SHEET A 1.5 - THERE IS ONLY ONE EXIT INDICATED FROM |
| | THE BASEMENT. |
| | |
| | A TRAVEL DISTANCE IS INDICATED AS 89'6" |
| | |
| | PER NFPA 101 CH 7 |
| | |
| | 36.2.4 NUMBER OF MEANS OF EGRESS. |
| | 36.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE |
| | FOLLOWING, |
| | EXCEPT AS OTHERWISE PERMITTED BY 36.2.4.2 THROUGH |
| | 36.2.4.5: |
| | (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 7.4. |
| | (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED |
| | ON EVERY |
| | STORY. |
| | (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE |
| | ACCESSIBLE FROM |
| | EVERY PART OF EVERY STORY. |
| | |
| | 36.2.4.3 A SINGLE MEANS OF EGRESS SHALL BE PERMITTED IN |
| | A CLASS C |
| | MERCANTILE OCCUPANCY, PROVIDED THAT THE TRAVEL DISTANCE |
| | TO THE EXIT |
| | OR TO A MALL PEDESTRIAN WAY (SEE 36.4.4.2) DOES NOT |
| | EXCEED 75 FT |
| | (23 M). |
| | |
| | 36.2.4 NUMBER OF MEANS OF EGRESS. |
| | 36.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE |
| | FOLLOWING, |
| | EXCEPT AS OTHERWISE PERMITTED BY 36.2.4.2 THROUGH |
| | 36.2.4.5: |
| | (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 7.4. |
| | (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED |
| | ON EVERY |
| | STORY. |
| | (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE |
| | ACCESSIBLE FROM |
| | EVERY PART OF EVERY STORY. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 3) SHEET A 1.5 - THE STORAGE OCCUPANCY DOES NOT APPEAR |
| | TO BE SEPARATED BY ANY FIRE RATING. |
| | |
| | PER NFPA 101, CH 6 |
| | |
| | 6.1.14 MULTIPLE OCCUPANCIES. |
| | 6.1.14.1 GENERAL. |
| | 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF |
| | 6.1.14.1 AND ONE OF THE FOLLOWING: |
| | (1) MIXED OCCUPANCIES ? 6.1.14.3 |
| | (2) SEPARATED OCCUPANCIES ? 6.1.14.4 |
| | |
| | THE CODE REQUIRES A 2 HOUR FIRE RATED SEPARATION. |
| | |
| | IS THIS A MIXED OR SEPARATED OCCUPANCY? |
| | |
| | PLEASE ALSO BE AWARE OF THE HAZARD CLASSIFICATION AND |
| | PROTECTION |
| | |
| | 6.2 HAZARD OF CONTENTS. |
| | 6.2.1 GENERAL. |
| | 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF |
| | CONTENTS SHALL |
| | BE THE RELATIVE DANGER OF THE START AND SPREAD OF FIRE, |
| | THE DANGER OF |
| | SMOKE OR GASES GENERATED, AND THE DANGER OF EXPLOSION |
| | OR OTHER |
| | OCCURRENCE POTENTIALLY ENDANGERING THE LIVES AND SAFETY |
| | OF THE |
| | OCCUPANTS OF THE BUILDING OR STRUCTURE. |
| | 6.2.1.2 HAZARD OF CONTENTS SHALL BE CLASSIFIED BY THE |
| | REGISTERED |
| | DESIGN PROFESSIONAL (RDP) OR OWNER AND SUBMITTED TO THE |
| | AUTHORITY HAVING JURISDICTION FOR REVIEW AND APPROVAL |
| | ON THE BASIS |
| | OF THE CHARACTER OF THE CONTENTS AND THE PROCESSES OR |
| | OPERATIONS |
| | CONDUCTED IN THE BUILDING OR STRUCTURE. |
| | 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT |
| | DEGREES OF |
| | HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS OF A |
| | BUILDING OR STRUCTURE, |
| | THE MOST HAZARDOUS SHALL GOVERN THE CLASSIFICATION, |
| | UNLESS |
| | HAZARDOUS AREAS ARE SEPARATED OR PROTECTED AS SPECIFIED |
| | IN SECTION |
| | 8.7 AND THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH |
| | 43. |
| | |
| | CH 8 |
| | |
| | 8.7 SPECIAL HAZARD PROTECTION. |
| | 8.7.1 GENERAL. |
| | 8.7.1.1* PROTECTION FROM ANY AREA HAVING A DEGREE OF |
| | HAZARD |
| | GREATER THAN THAT NORMAL TO THE GENERAL OCCUPANCY OF |
| | THE |
| | BUILDING OR STRUCTURE SHALL BE PROVIDED BY ONE OF THE |
| | FOLLOWING |
| | MEANS: |
| | (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT |
| | WINDOWS THAT |
| | HAS A 1-HOUR FIRE RESISTANCE RATING IN ACCORDANCE WITH |
| | SECTION 8.3 |
| | (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING |
| | SYSTEMS IN |
| | ACCORDANCE WITH SECTION 9.7 |
| | (3) APPLYING BOTH 8.7.1.1(1) AND (2) WHERE THE HAZARD |
| | IS SEVERE |
| | OR WHERE OTHERWISE SPECIFIED BY CHAPTERS 11 THROUGH 43 |
| | |
| | 8.7.1.3 DOORS IN BARRIERS REQUIRED TO HAVE A FIRE |
| | RESISTANCE RATING |
| | SHALL HAVE A MINIMUM ?-HOUR FIRE PROTECTION RATING AND |
| | SHALL BE |
| | SELF-CLOSING OR AUTOMATIC-CLOSING IN ACCORDANCE WITH |
| | 7.2.1.8. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | 4) PER #3 ABOVE WHAT IS THE TYPE AND CLASSIFICATION OF |
| | THE STORGE CONTENTS. |
| | |
| | PER CH 6 |
| | |
| | 6.2.2 CLASSIFICATION OF HAZARD OF CONTENTS. |
| | 6.2.2.1* GENERAL. THE HAZARD OF CONTENTS OF ANY |
| | BUILDING OR |
| | STRUCTURE SHALL BE CLASSIFIED AS LOW, ORDINARY, OR HIGH |
| | IN |
| | ACCORDANCE WITH 6.2.2.2, 6.2.2.3, AND 6.2.2.4. |
| | 6.2.2.2* LOW HAZARD CONTENTS. LOW HAZARD CONTENTS SHALL |
| | BE |
| | CLASSIFIED AS THOSE OF SUCH LOW COMBUSTIBILITY THAT NO |
| | SELFPROPAGATING |
| | FIRE THEREIN CAN OCCUR. |
| | 6.2.2.3* ORDINARY HAZARD CONTENTS. ORDINARY HAZARD |
| | CONTENTS SHALL |
| | BE CLASSIFIED AS THOSE THAT ARE LIKELY TO BURN WITH |
| | MODERATE RAPIDITY OR |
| | TO GIVE OFF A CONSIDERABLE VOLUME OF SMOKE. |
| | 6.2.2.4* HIGH HAZARD CONTENTS. HIGH HAZARD CONTENTS |
| | SHALL BE |
| | CLASSIFIED AS THOSE THAT ARE LIKELY TO BURN WITH |
| | EXTREME RAPIDITY OR FROM |
| | WHICH EXPLOSIONS ARE LIKELY. (FOR MEANS OF EGRESS |
| | REQUIREMENTS, SEE |
| | SECTION 7. 11.) |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | 5) SHEET A 1.5 - THERE IS A DOUBLE DIRECTION SWING DOOR |
| | # 104 THAT SWINGS IN BOTH DIRECTION. |
| | |
| | A REQUIRED EXIT DOOR SHALL SWWING IN THE DIRECTION OF |
| | EXIT TRAVEL. |
| | |
| | CH 7 |
| | |
| | 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES |
| | REQUIRED TO BE |
| | OF THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING |
| | IN THE |
| | DIRECTION OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING |
| | CONDITIONS: |
| | (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD |
| | OF 50 OR |
| | MORE, EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE |
| | REQUIRED TO |
| | SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED |
| | BY 7.2.4.3.8.1 OR 7.2.4.3.8.2. |
| | (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED |
| | TO |
| | SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING |
| | HEALTH |
| | CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19. |
| | (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT |
| | ENCLOSURE, UNLESS |
| | THE DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT |
| | OPENS |
| | DIRECTLY INTO AN EXIT ENCLOSURE |
| | (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD |
| | CONTENTS AREA |
| | |
| | THE INTENT OF THE ABOVE CODE IS THAT A DOOR MUST SWING |
| | IN THE DIRECTION OF TRAVEL BUT CAN SWING IN THE |
| | OPPISITE DIRECTION IF LESS THAN 50; IT CAN NOT SWING |
| | BOTH WAYS. ONE OR THE OTHER. |
| | |
| | PLEASE REIVIEW AND CORRECT. |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |