| Plan Review Notes For Permit 20090076 |
| Permit Number |
20090076 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-09-25 08:59:32 | DOOR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE STRUCTURAL CALCULATIONS TO DETERMINE | | | THE OPENING REQUIRED WIND DESIGN PRESSURES OR PROVIDE | | | SIGNED AND SEALED WIND DESIGN PRESSURES FOR THE OPENING | | | FROM AN ARCHITECT OR ENGINEER FBC 1609.1.1 (RISK | | | CATEGORY IV BUILDING - 180MPH WIND SPEEDS) | | | | | | FYI - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO | | | BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - | | | IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL | | | SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE | | | ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG | | | WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON | | | FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW | | | REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected] | | | AND ASKING FOR THE FORM. |
|