| 2020-09-11 10:13:46 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20090022 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) CANNOT COMPLETE THE REVIEW, NOT ENOUGH INFORMATION |
| | GIVEN IN THIS SUBMITTAL. |
| | |
| | 2) PLEASE IDENTIFY THE WEIGHT OF THE GENERATOR IN THE |
| | GENERATOR SPEC SHEET SUBMITTED. FBC FS 107.2.1 |
| | |
| | 3) PLEASE IDENTIFY THE GENERATOR USED AND THE WEIGHT OF |
| | GENERATOR ON THE GENERATOR PAD SPECS PROVIDED. FBC FS |
| | 107.2.1 |
| | |
| | 4) PLEASE IDENTIFY REGULATOR USED IN THE SUBMITTED |
| | REGULATOR PACKAGE. FBC FS 107.2.1 |
| | |
| | 5) PLEASE PROVIDE METHOD USED TO SIZE THIS NATURAL GAS |
| | PIPING SYSTEM, I.E.; LONGEST LENGTH OR BRANCH LENGTH |
| | METHOD? FBC FS 107.2.1 |
| | |
| | 6) PLEASE PROVIDE THE DISTANCE TO THE MOST REMOTE |
| | APPLIANCE FROM THE GAS METER FOR SIZING OF THIS SYSTEM. |
| | FBC FS 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |