| 2021-01-27 15:10:04 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 200900001 |
| | 1/27/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) COMMENT #1 FROM THE 1ST REVIEW PRINTED BELOW HAS NOT |
| | BEEN ADDRESSED AND THE PERMIT FOR THE GAS LINE TO THE |
| | GENERATOR CANNOT BE ISSUED UNTIL THE EXISTING GAS |
| | SYSTEM RECEIVES A PERMIT. YOUR SCOPE OF WORK SHOWS |
| | CONNECTION OF THE NEW GAS LINE TO THE EXISTING |
| | UNPERMITTED GAS LINE, BUT ALSO SHOWS THE EXISTING |
| | PIPING TO BE OUT OF YOUR SCOPE. CONNECTING TO AN |
| | UNPERMITTED AND UNINSPECTED GAS LINE COULD POTENTIALLY |
| | BE A LIFE SAFETY ISSUE. IN ORDER TO MOVE FORWARD, |
| | PLEASE CLARIFY IF YOUR PERMIT AND SCOPE OF WORK WILL |
| | INCLUDE THE EXISTING PIPING OR WILL BE LEGALLY |
| | PERMITTED BY ANOTHER LICENSED CONTRACTOR. |
| | 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 2224 EMBASSY |
| | DR. SHOW EXPIRED PERMITS FOR A NEW GENERATOR AND GAS |
| | PIPING TO THE GENERATOR: PERMITS- 06090324 & 06090326. |
| | THE GAS RISER YOU HAVE SUBMITTED FOR THE NEW GENERATOR |
| | INDICATES AN "EXISTING" 3/4 IN. UG PE PIPE, HOWEVER |
| | THERE IS NO PERMIT AND INSPECTION RECORD FOR THE |
| | INSTALLATION OF THE LINE. IT APPEARS THAT IT MAY HAVE |
| | BEEN INSTALLED WITHOUT A PERMIT. IN ADDITION, I AM |
| | UNABLE TO FIND ANY RECORDS FOR GAS PIPING INSTALLATIONS |
| | IN THE INTERIOR OF THE RESIDENCE, AND THE RISER IS |
| | INDICATING THESE GAS LOADS AS EXISTING. IT APPEARS THAT |
| | THE INTERIOR INSTALLATIONS MAY HAVE ALSO BEEN DONE |
| | WITHOUT A PERMIT, OR PRE-DATE RECORDS ON FILE. IF THE |
| | INSTALLATIONS WERE DONE WITHOUT A PERMIT, THEN THE |
| | ENTIRE SYSTEM MUST BE REVIEWED AS A NEW SYSTEM- |
| | SECTIONS 105.1 & 107.2.1 WPB. PLEASE PROVIDE A COMPLETE |
| | RISER DRAWING THAT INCLUDES THE BRANCH LINE TO THE |
| | INTERIOR APPLIANCES, BRANCH LINE TO THE GENERATOR, AND |
| | ANY OTHER EXISTING BRANCH LINES. SHOW THE TOTAL LENGTHS |
| | OF THE BRANCHES, AND THE TOTAL DEVELOPED LENGTH OF THE |
| | SYSTEM FROM THE METER TO THE MOST REMOTE OUTLET. YOU |
| | ARE INDICATING THE EXISTING LOAD AT 135,000 BTUH. SHOW |
| | ON THE RISER THE INDIVIDUAL APPLIANCE LOCATIONS AND |
| | THEIR INDIVIDUAL LOADS- REFER TO SECTIONS G2412.3, |
| | G2412.4, G2413.1, & G2413.2 FBC RES. FUEL GAS. |
| | |
| | NEW COMMENTS BASED ON RESUBMITTED DRAWINGS. |
| | |
| | 1) PLEASE INDICATE THE PURPOSE OF THE CAPPED 1-1/4 AND |
| | 1/2 IN. RIGID GAS PIPES ON THE NEW RISER DRAWING. ARE |
| | THESE THE LINES FOR FUTURE APPLIANCES AND ARE THE CAPS |
| | ON THE INTERIOR OR EXTERIOR OF THE HOUSE?- SECTIONS |
| | G2412.4 FBC RES. |
| | |
| | 2) PLEASE PROVIDE A GAS TIGHT CAP FOR THE PIPE TO THE |
| | REMOVED POOL HEATER. CLARIFY IF A NEW HEATER WILL BE |
| | INSTALLED IN THE FUTURE- SECTIONS G2412.4 & G2415.15. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |