| 2020-10-07 16:22:19 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 200900001 |
| | 10/7/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 2224 EMBASSY |
| | DR. SHOW EXPIRED PERMITS FOR A NEW GENERATOR AND GAS |
| | PIPING TO THE GENERATOR: PERMITS- 06090324 & 06090326. |
| | THE GAS RISER YOU HAVE SUBMITTED FOR THE NEW GENERATOR |
| | INDICATES AN "EXISTING" 3/4 IN. UG PE PIPE, HOWEVER |
| | THERE IS NO PERMIT AND INSPECTION RECORD FOR THE |
| | INSTALLATION OF THE LINE. IT APPEARS THAT IT MAY HAVE |
| | BEEN INSTALLED WITHOUT A PERMIT. IN ADDITION, I AM |
| | UNABLE TO FIND ANY RECORDS FOR GAS PIPING INSTALLATIONS |
| | IN THE INTERIOR OF THE RESIDENCE, AND THE RISER IS |
| | INDICATING THESE GAS LOADS AS EXISTING. IT APPEARS THAT |
| | THE INTERIOR INSTALLATIONS MAY HAVE ALSO BEEN DONE |
| | WITHOUT A PERMIT, OR PRE-DATE RECORDS ON FILE. IF THE |
| | INSTALLATIONS WERE DONE WITHOUT A PERMIT, THEN THE |
| | ENTIRE SYSTEM MUST BE REVIEWED AS A NEW SYSTEM- |
| | SECTIONS 105.1 & 107.2.1 WPB. PLEASE PROVIDE A COMPLETE |
| | RISER DRAWING THAT INCLUDES THE BRANCH LINE TO THE |
| | INTERIOR APPLIANCES, BRANCH LINE TO THE GENERATOR, AND |
| | ANY OTHER EXISTING BRANCH LINES. SHOW THE TOTAL LENGTHS |
| | OF THE BRANCHES, AND THE TOTAL DEVELOPED LENGTH OF THE |
| | SYSTEM FROM THE METER TO THE MOST REMOTE OUTLET. YOU |
| | ARE INDICATING THE EXISTING LOAD AT 135,000 BTUH. SHOW |
| | ON THE RISER THE INDIVIDUAL APPLIANCE LOCATIONS AND |
| | THEIR INDIVIDUAL LOADS- REFER TO SECTIONS G2412.3, |
| | G2412.4, G2413.1, & G2413.2 FBC RES. FUEL GAS. |
| | |
| | A) SHOW THE DELIVERY PRESSURE AT THE OUTLET OF THE NEW |
| | REGULATOR, AND THE REQUIRED PIPE UNIONS WITHIN 1 FT. OF |
| | EITHER SIDE OF THE REGULATOR- SECTIONS G2421.1 & |
| | G2421.2(7). |
| | |
| | B) INDICATE THE MAKE AND MODEL OF THE REGULATOR ON THE |
| | RISER AND MARK OR HIGHLIGHT THE SPECS TO SHOW THE |
| | SELECTED MODEL, THE MAX INLET AND OUTLET SIZE AND |
| | PRESSURES, AND ORIFICE SIZE. |
| | |
| | 2) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| | SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 |
| | WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| | PLEASE INCLUDE A TITLE BLOCK ON THE DRAWING THAT |
| | INCLUDES CONTRACTOR OR COMPANY NAME AND LICENSE NUMBER. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |