| 2020-09-18 14:34:33 | PROVISO: FBC EC R4.3.3.6 AIR HANDLING UNITS |
| | AIR HANDLER MAY BE INSTALLED IN THE ATTIC ONLY IF THE |
| | FOLLOWING CONDITIONS ARE MET. |
| | 1) THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN |
| | 6 FEET OF AN ATTIC ACCESS. |
| | 2) A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT |
| | DOWN THE UNIT WHEN THE CONDENSATION DRAIN IS NOT |
| | WORKING PROPERLY. |
| | 3) THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO |
| | REPLACE THE AIR HANDLER. |
| | 4) A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL |
| | INDICATING TO THE HOME OWNER THAT THE AIR HANDLER IS |
| | LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL |
| | CAPITALS, IN 16-POINT TYPE WITH THE TITLE AND FIRST |
| | PARAGRAPH IN BOLD: |
| | NOTICE TO HOMEOWNER |
| | |
| | A PART OF YOUR AIR-CONDITIONING SYSTEM, THE AIR |
| | HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT |
| | AND ECONOMIC OPERATION OF THE AIR CONDITIONING SYSTEM, |
| | YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED. |
| | YOUR AIR CONDITIONING SYSTEM IS EQUIPED WITH ONE OR |
| | BOTH OF THE FOLLOWING: (1) A DEVICE THAT WILL ALERT YOU |
| | WHEN THE CONDENSATION DRAIN IS NOT WORKING PROPERLY OR |
| | (2) A DEVICE THAT WILL SHUT DOWN THE SYSTEM WHEN THE |
| | CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL |
| | DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF |
| | SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER |
| | WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF |
| | PEAK OPERATION. |
| | |