| Plan Review Notes For Permit 20081429 |
| Permit Number |
20081429 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-10-21 13:11:18 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) ONE BATHROOM NEEDS TO HAVE A 29" DOOR OPENING | | | CLEARANCE AT TOILET ROOM. FBC R320.1.1 - PLEASE SHOW | | | HOW THE 2'6" DOOR WILL ALLOW A CLEAR WIDTH OF 29" - FBC | | | ACCESSIBILITY 404.2.3 CLEAR OPENINGS OF DOORWAYS WITH | | | SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF | | | THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. | | | | | | | | | |
|