| Date |
Text |
| 2020-10-05 10:13:26 | 10/05/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE PROVIDE PUMP CURVE AND SHOW ON THE POOL PUMP |
| | CURVE WHICH CURVE KEY IS SPECIFIC TO THE PUMP BEING |
| | INSTALLED ON THIS POOL. THIS IS NEEDED TO CONFIRM THE |
| | MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS PER THE |
| | ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. |
| | |
| | 2. PLEASE SUBMIT SPECIFICATIONS FOR THE PUMP AND |
| | CARTRIDGE FILTER PER THE WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | |
| | 3. THIS IS A MULTI-FAMILY DWELLING, IF THERE ARE NOT |
| | TWO METERS FOR WATER USERS IT WILL REQUIRE TO INSTALL A |
| | BACKFLOW PREVENTION ASSEMBLY AT THE POINT OF DELIVERY. |
| | THE TYPE OF BACKFLOW ASSEMBLY REQUIRED WILL BE |
| | DEPENDENT UPON THE DEGREE OF HAZARD POSED BY THE WATER |
| | USER. IF ONE METER THIS PROPERTY WILL REQUIRE A REDUCED |
| | PRESSURE ZONE ASSEMBLY VACUUM BREAKER. A PERMIT IS |
| | REQUIRED BY A LICENSED CONTRACTOR AND MUST BE CERTIFIED |
| | BY UTILITIES BEFORE FINAL INSPECTION. PLEASE CONTACT |
| | THE CITY OF WPB UTILITIES AT 561-822-2240 FOR FURTHER |
| | DIRECTIONS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |