| 2021-01-07 08:55:08 | 01/07/20 3RD PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | THIS IS THE THIRD PLAN REVIEW THAT HAS NOT PASSED. |
| | PLEASE GET WITH THE PLAN REVIEWER AND MAKE AN |
| | APPOINTMENT TO COME INTO THE BUILDING DEPARTMENT TO |
| | EXPLAIN WHAT IS NEEDED. |
| | |
| | 1. PLEASE SHOW THE BUILDING USE (OCCUPANCY |
| | CLASSIFICATION PER FBC CHAPTER 3. |
| | |
| | 2. PLEASE SHOW THE WALL AND FLOOR FINISHES TO COMPLY |
| | WITH FBC 1210.2.2. EPOXY PAINT ON DRYWALL DOES NOT MEET |
| | THE INTENT OF THE CODE. |
| | |
| | 3. PLEASE SHOW THE BOTTOM OF THE MIRROR'S REFLECTIVE |
| | SURFACE TO THE FINISHED FLOOR TO COMPLY WITH FBC |
| | ACCESSIBILITY 603.3 MIRRORS, NOT THE MIRROR'S FRAME. |
| | |
| | 4. THE 24" AND 12" ON THE GRAB BAR BEHIND THE TOILET |
| | NEED TO BE SHOWN FROM THE CENTERLINE OF THE WATER |
| | CLOSET, NOT TO THE EDGE OF THE TOILET SEE FBC |
| | ACCESSIBILITY FIGURE 604.5.2. |
| | |
| | 5. TOILET PAPER DISPENSER - THE 7" TO 9" NEEDS TO BE |
| | SHOWN TO THE CENTER OF THE DISPENSER, REMOVE THE 9?? |
| | AND PUT 15? TO TOP OF DISPENSER SEE FBC ACCESSIBILITY |
| | FIGURE 604.7. |
| | |
| | 6. PLEASE SHOW THE REQUIRED CLEAR FLOOR SPACE AND |
| | DIMENSIONS FOR THE TOILET AND LAVATORY IN THE TOILET |
| | ROOM PER FBC-ACCESS. SECS. 604.3.1 AND FIGURE 604.3.1 |
| | AND 606..2 AND SECS.305 & 306. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |