| Plan Review Notes For Permit 20081406 |
| Permit Number |
20081406 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-12-16 16:01:41 | ADD RESTROOM | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | 3RD REVIEW | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE BUILDING USE (OCCUPANCY | | | CLASSIFICATION PER FBC CHAPTER 3. | | | 2) PLEASE SHOW THE RESTROOM WALL AND FLOOR FINISHES TO | | | COMPLY WITH FBC 1210.2 (DRYWALL IS NOT CONSIDERED A | | | HARD SURFACE) | | | 3) PLEASE SHOW THE BOTTOM OF THE MIRROR REFLECTION TO | | | THE FINISHED FLOOR TO COMPLY WITH FBC ACCESSIBILITY | | | 603.3 MIRRORS. | | | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL | | | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING | | | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND. | | | 4) THE TOILET PAPER DISPENSER = SEE FBC ACCESSIBILITY | | | FIGURE 604.7 | | | 5) PLEASE SHOW THE BUILDING EXIT DOOR AND THE RESTROOM | | | DOOR MANUVERING CLEARANCE TO COMPLY WITH FBC | | | ACCESSIBILITY 404.2.4 SEE FIGURE 404.2.4.1 | | | |
|