| 2020-09-15 07:07:24 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20081400 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) DESIGNER OF THE ENERGY GAUGE DOCUMENT NEEDS TO FILL |
| | IN THE ?PREPARED BY? AREA OF THE DOCUMENT. ALSO ON PAGE |
| | 2 OF THIS DOCUMENT PLEASE ADD THE PHYSICAL ADDRESS OF |
| | THIS NEW SFD. FBC FS 107.2.1 |
| | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN |
| | IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A |
| | DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY |
| | VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A |
| | SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING |
| | DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1; |
| | FS 471/481 |
| | |
| | 3) PLEASE PROVIDE ADDRESS FOR THIS PROJECT ON THE |
| | MANUAL J CALCULATIONS. FBC FS 107.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |