| Plan Review Notes For Permit 20081396 |
| Permit Number |
20081396 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-08-31 11:45:47 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) PLEASE PROVIDE A DETAILED NARRATIVE OF WHAT THESE | | | TENTS WILL BE USED FOR AND WHAT TYPE OF EVENTS ARE | | | PROPOSED? | | | | | | PLEASE PROVIDE DETAL FOR EACH TENT AND WITHIN THE GATED | | | AREA. | | | | | | | | | | | | 1A) THERE ARE NO FLOOR PLANS SHOWING INTERIOR LAYOUTS | | | TO ENSURE OPEN WALKWAYS THAT LEAD TO EXITS. | | | | | | PLEASE PROVIDE DETAILED FLOOR PALNS INCLUDING ALL | | | EXITS. | | | | | | | | | | | | 2) THERE ARE NO INDICATIONS OF POWER SUPPLIES/LIGHTING. | | | | | | PLEASE PROVIDE POWER DETAILS, INCLUDING ALL LOCATIONS | | | OF GENERATORS. | | | | | | | | | Y | | | 3) THERE ARE NO IDICATIONS OF TIE DOWNS/ANCHORING. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | 4) THERE ARE NO INDICATIONS OF THE SIZE OF THE FENCE | | | GATES OR HOW THE CAN BE OPENED TO EXIT. | | | | | | PLEAE PROVIDE FENCE GATE DETAILS. | | | | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|