Plan Review Notes
Plan Review Notes For Permit 20081388
Permit Number 20081388
Review Stop P
Sequence Number 1
Notes
Date Text
2020-09-09 15:18:3109/09/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.
  
 3. SUBMIT A SLAB REPAIR DETAIL AND SHOW THE WIDTH OF
 THE REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO BE
 REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE
 AND LENGTH OF THE DOWELS, THE MINIMUM EMBEDMENT DEPTH
 INTO THE EXISTING SLAB, THE ANCHORING MATERIAL FOR THE
 DOWELS AND THE SPACING OF THE DOWELS ON CENTER. THE
 REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL
 AND THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR A FINAL INSPECTION.
  
 4. PLUMBING RISER DIAGRAM FOR REQUIRED FOR SANITARY AND
 WATER (SHOWING PIPE SIZES, LOCATIONS OF SHUTOFF VALVES,
 WATER HAMMER ARRESTORS, MIXING VALVES ) PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL
 PLUMBING.
  
 5. PLEASE SHOW SOURCE OF HOT WATER AND LAVE SHALL HAVE
 TEMPERED SHALL BE 110 DEGREES WITH A DEVICE THAT
 COMPLIES TO ASSE 1070 PER THE 2017 FBC SEC. P 607.1.2.
  
 6. STAFF BATHROOM IN COMMON USE AREA NEED TO COMPLY
 2017 FBC ACC SEC. 213.2 AS FOLLOWS;
  
 A. PLEASE SHOW THE DISTANCE FROM THE WATER CLOSET TO
 THE WALL PER THE 2017 FBC ACC SEC. 604.1.
  
 B. PLEASE SHOW THE CLEAR FLOOR SPACE FOR TOILET AND LAV
 WITH DIMENSION PER 2017 FBC ACC. SEC. 604.3.1.
  
 C. PLEASE SHOW THE TOILET PAPER HOLDER PER THE 2017
 FBC ACC SEC. 604.7.
  
 D. PLEASE SHOW THE REFLECTIVE PART OF THE MIRROR TO BE
 THE OF 40? TO THE REFLECTIVE SIDE PER THE 2017 FBC ACC
 SEC. 603.3.
  
 E. PLEASE SHOW GRAB BARS DETAILS PER THE 2017 FBC ACC
 SEC. 604.5.2.
  
 F. PLEASE SHOW TOW CLEARANCE FOR LAV IN ACCORDANCE WITH
 2017 FBC ACC SEC. 306.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved