| Date |
Text |
| 2020-09-09 15:18:31 | 09/09/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 2. SIGNED AND SEALED DRAWINGS NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR - |
| | IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL |
| | SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE |
| | ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN |
| | REVIEW REQUEST FORM" EXPLAINING THE REASON FOR |
| | SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW |
| | REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected] |
| | AND ASKING FOR THE FORM. |
| | |
| | 3. SUBMIT A SLAB REPAIR DETAIL AND SHOW THE WIDTH OF |
| | THE REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO BE |
| | REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE |
| | AND LENGTH OF THE DOWELS, THE MINIMUM EMBEDMENT DEPTH |
| | INTO THE EXISTING SLAB, THE ANCHORING MATERIAL FOR THE |
| | DOWELS AND THE SPACING OF THE DOWELS ON CENTER. THE |
| | REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL |
| | AND THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED |
| | SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE |
| | FOR A FINAL INSPECTION. |
| | |
| | 4. PLUMBING RISER DIAGRAM FOR REQUIRED FOR SANITARY AND |
| | WATER (SHOWING PIPE SIZES, LOCATIONS OF SHUTOFF VALVES, |
| | WATER HAMMER ARRESTORS, MIXING VALVES ) PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL |
| | PLUMBING. |
| | |
| | 5. PLEASE SHOW SOURCE OF HOT WATER AND LAVE SHALL HAVE |
| | TEMPERED SHALL BE 110 DEGREES WITH A DEVICE THAT |
| | COMPLIES TO ASSE 1070 PER THE 2017 FBC SEC. P 607.1.2. |
| | |
| | 6. STAFF BATHROOM IN COMMON USE AREA NEED TO COMPLY |
| | 2017 FBC ACC SEC. 213.2 AS FOLLOWS; |
| | |
| | A. PLEASE SHOW THE DISTANCE FROM THE WATER CLOSET TO |
| | THE WALL PER THE 2017 FBC ACC SEC. 604.1. |
| | |
| | B. PLEASE SHOW THE CLEAR FLOOR SPACE FOR TOILET AND LAV |
| | WITH DIMENSION PER 2017 FBC ACC. SEC. 604.3.1. |
| | |
| | C. PLEASE SHOW THE TOILET PAPER HOLDER PER THE 2017 |
| | FBC ACC SEC. 604.7. |
| | |
| | D. PLEASE SHOW THE REFLECTIVE PART OF THE MIRROR TO BE |
| | THE OF 40? TO THE REFLECTIVE SIDE PER THE 2017 FBC ACC |
| | SEC. 603.3. |
| | |
| | E. PLEASE SHOW GRAB BARS DETAILS PER THE 2017 FBC ACC |
| | SEC. 604.5.2. |
| | |
| | F. PLEASE SHOW TOW CLEARANCE FOR LAV IN ACCORDANCE WITH |
| | 2017 FBC ACC SEC. 306. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |