| 2020-09-17 22:43:37 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ELECTRICAL SUB-PERMIT APPLICATION SAYS "FIXTURE |
| | REPLACEMENTS". THERE IS MORE WORK THAN "FIXTURE |
| | REPLACMENT ONLY" SHOWN ON PLAN. PROVIDE PERMIT |
| | APPLICATION WITH ACCURATE DESCRIPTION. FBC 107.2.1 |
| | |
| | 2. PROVIDE PLAN THAT CLEARLY ANNOTATES WORK TO BE |
| | COMPLETED. IS THIS A FULL GUT REMODEL OF APARTMENT? IF |
| | SO, THE PLAN PROVIDED IS NOT TO CURRENT 2014 NEC. |
| | PROVIDE CORRECTIONS. |
| | |
| | 3. PROVIDE NOTE ON PLAN THAT LOW VOLTAGE SHOWN WILL |
| | REQUIRE SEPARATE PERMIT. FBC 107.2.1 105.1 |
| | |
| | 4. SMOKE DETECTORS ARE TO BE HARD WIRED PER FBC-R 314& |
| | 315. NOTES ON PLAN ARE CONFLICTING AND STATE THAT |
| | "SMOKE ALARMS ARE EXISTING 10 YEAR BATTERY" THEN |
| | ANOTHER NOTES STATES "SMOKE ALARMS WILL BE HARD WIRED". |
| | |
| | 5. WITH INFORMATION AND PLAN PROVIDED A COMPLETE REVIEW |
| | COULD NOT BE MADE. SUBMIT PLAN WITH CLEAR SCOPE OF |
| | WORK. ADDITIONAL PLAN REVIEW COMMENT MAY OCCUR AFTER |
| | RESUBMISSION. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |