| 2020-10-06 12:26:02 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20081355 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) WE HAVE NO RECORDS OF A PERMITTED MECHANICAL SYSTEM |
| | FOR THIS ADDRESS. WE MUST CONSIDER THIS AS A NEW SYSTEM |
| | AND NOT A CHANGE OUT. PLEASE PROVIDE THE ENERGY |
| | CALCULATIONS AND THE MANUAL J FOR THIS PROJECT. FBC E |
| | 101.5.1.1.2 AND FBC EC R 403.7 |
| | |
| | 2) IT APPEARS THAT THE ENTIRE DUCTWORK IS NEW. PLEASE |
| | UPDATE THE PERMIT APPLICATION TO REFLECT A NEW |
| | MECHANICAL SYSTEM FOR THIS ADDRESS. FBC 107.2.1 |
| | |
| | 3) IT APPEARS THE VALUE FOR THIS NEW SYSTEM IS LOW. |
| | PLEASE ADJUST THE VALUE ON THE APPLICATION. FBC 109.3 |
| | |
| | 4) PLEASE PROVIDE DUCT SIZES ON THE DRAWING FOR THE |
| | RETURN DUCTS. PLEAS MAKE SURE THEY MEET: FBC RES |
| | M1602.3 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |