| Date |
Text |
| 2020-09-15 09:38:20 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20081311 2277 PALM BEACH LAKES BLVD |
| | |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED; SEE ITEM 2 COMMENT BELOW |
| | |
| | 1. PER WPB FBC 107.2.1, CLEARLY INDICATE ON PLAN SHEET |
| | 5 OF 7 WHETHER THE PLUMBING PLAN OR THE OPTIONAL |
| | PLUMBING PLAN IS APPLICABLE; SANITARY AND WATER RISERS |
| | SHALL REFLECT THE APPLICATION. |
| | COMMENT |
| | SEE PLAN SHEET 5 OF 7 PLUMBING PROVISO: PER PERMIT |
| | APPLICANT?S RESPONSE LETTER DATED 9/4/2020, THE |
| | PLUMBING PLAN IS APPLICABLE. |
| | |
| | 2. PER WPB FBC 107.2.1, CLEARLY INDICATE ON THE SURVEY |
| | THE METER AND BACKFLOW PREVENTER DESIGNATED TO PROVIDE |
| | POTABLE WATER TO THE UNIT. PROVIDE ROUTING AND SIZING |
| | OF WATER SERVICE TO THE POINT OF CONNECTION AT THE |
| | TRAILER. PROVIDE SPEC/DETAIL FOR LEAD FREE RPZ BFP. |
| | COMMENT |
| | SEE PLAN SHEET SURVEY DENIED REGARDING THE PERMIT |
| | APPLICANT?S RESPONSE LETTER DATED 9/4/2020, PER FBC PL |
| | 602.3, THE USE OF FRESH WATER SUPPLY TANK CONNECTED TO |
| | THE INTERNAL SYSTEM IS NOT PERMITTED AS THERE IS |
| | POTABLE CITY UTILITIES WATER AVAILABLE; PROVIDE ROUTING |
| | AND SIZING OF WATER SERVICE TO THE POINT OF CONNECTION |
| | TO THE TRAILER. PER WPB FBC 107.2.1, PROVIDE |
| | SPEC/DETAIL OF LEAD FREE RPZ AND COMPLY WITH THE |
| | REQUIREMENTS OF FBC PL SECTION 608. |
| | |
| | 3. PER WPB FBC 107.2.1, CLEARLY INDICATE ON THE SURVEY |
| | ONE OF THE FOLLOWING; |
| | A. THE CAPACITY AND LOCATION OF A PORTABLE SANITARY |
| | HOLDING TANK |
| | B. PROVIDE A BUILDING SEWER AND CONNECTION TO THE CITY |
| | SEWAGE SYSTEM |
| | COMMENT |
| | SEE PLAN SHEET SURVEY AND PLAN SHEET 5 OF 7 PLUMBING |
| | PROVISO: PER PERMIT APPLICANT?S RESPONSE LETTER DATED |
| | 9/4/2020, A 275 GALLON SANITARY HOLDING TANK IS TO BE |
| | LOCATED AT THE HITCH END OF THE TRAILER. |
| | |
| | 4. PER WPB FBC 107.2.1, CLEARLY INDICATE THE FUEL |
| | SOURCE AND TYPE FOR THE PORTABLE GENERATORS NOTED ON |
| | THE SURVEY. |
| | COMMENT |
| | SEE PLAN SHEET SURVEY PER PERMIT APPLICANT?S RESPONSE |
| | LETTER DATED 9/4/2020, EACH USE TYPE 2 DIESEL, EQUIPPED |
| | WITH 90 GALLON FUEL TANK. EXTRA TANK SIZE 500 GALLON. |
| | THIS RESPONSE HAS BEEN REFERRED TO MECHANICAL PLANS |
| | EXAMINER FOR REVIEW. |
| | |
| | |
| | |
| | PROVISO: ACCESSIBILITY; SEE PLAN PAGE 1 OF 7 |
| | A. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| | OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 |
| | INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC |
| | ACC 604.2 |
| | B. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND |
| | 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR |
| | WALL PER FBC ACC 604.3.1 |
| | C. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| | MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE |
| | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR |
| | WALL PER FBC ACC 604.5.1 |
| | D. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| | MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 |
| | E. FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. |
| | HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. |
| | FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE |
| | WATER CLOSET PER FBC ACC 604.6 |
| | F. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC |
| | ACC 604.8. |
| | G. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| | FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES |
| | (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS |
| | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER |
| | FBC ACC 604.4. |
| | H. PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A |
| | HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT |
| | THE CENTER) OF THE GRIPPING SURFACE, |
| | I. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE |
| | FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC |
| | ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS |
| | REQUIRED BY FBC ACC 306.2 AND 306.3 |
| | J. UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE |
| | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH |
| | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2 |
| | K. DRINKING FOUNTAINS SHALL COMPLY WITH 307 AND 602 PER |
| | FBC ACC 602.1. |
| | L. UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE |
| | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH |
| | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2. |
| | M. OPERABLE PARTS SHALL COMPLY WITH 309 PER FBC ACC |
| | 602.3. |
| | N. SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC 602.4. |
| | O. THE SPOUT SHALL BE LOCATED 15 INCHES (380 MM) |
| | MINIMUM FROM THE VERTICAL SUPPORT AND 5 INCHES (125 MM) |
| | MAXIMUM FROM THE FRONT EDGE OF THE UNIT, INCLUDING |
| | BUMPERS PER FBC ACC 602.5. |
| | P. THE SPOUT SHALL PROVIDE A FLOW OF WATER 4 INCHES |
| | (100 MM) HIGH MINIMUM AND SHALL BE LOCATED 5 INCHES |
| | (125 MM) MAXIMUM FROM THE FRONT OF THE UNIT. THE ANGLE |
| | OF THE WATER STREAM SHALL BE MEASURED HORIZONTALLY |
| | RELATIVE TO THE FRONT FACE OF THE UNIT. WHERE SPOUTS |
| | ARE LOCATED LESS THAN 3 INCHES (75 MM) OF THE FRONT OF |
| | THE UNIT, THE ANGLE OF THE WATER STREAM SHALL BE 30 |
| | DEGREES MAXIMUM. WHERE SPOUTS ARE LOCATED BETWEEN 3 |
| | INCHES (75 MM) AND 5 INCHES (125 MM) MAXIMUM FROM THE |
| | FRONT OF THE UNIT, THE ANGLE OF THE WATER STREAM SHALL |
| | BE 15 DEGREES MAXIMUM PER FBC ACC 602.6. |
| | Q. SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING |
| | PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 |
| | INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND PER FBC ACC 607.2. |
| | R. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| | REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE |
| | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| | BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890 |
| | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC |
| | ACC 603.3. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20081311 2277 PALM BEACH LAKES BLVD |
| | |
| | |
| 2020-09-10 08:19:17 | FOR JERRY SMITH |