2020-10-04 14:53:26WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20081311
 ADD: 2277 PALM BEACH LAKES BLVD.
 CONT: TBD/ TO BE DETERMINED
 TEL: 281-960-9605
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SUN. OCT. 04TH/2020
 ACTION: DENIED
  
 NOTICE: FOR BUILDING REVIEW NO TRANSMITTAL LETTER WAS
 SUBMITTED. PLANS DO NOT RELECT A VERSION 2.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 4X FEE / NOTICE!!!!! FLORIDA STATUTE 553.80(2)(B)
  
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS?
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
 SECOND REQUEST FOR ALL COMMENTS:
 1) UNDER FLORIDA LICENSING LAWS A LICENSED COMPANY/
 INDIVIDUAL (QUALIFIER) MUST APPLY FOR A PERMIT TO
 INSTALL A MANUFACTURED BUILDING. WE COULD NOT SEE WHERE
 SATELLITE STRUCTURES HAS ANY FLORIDA LICENSING.
  
 2) PLEASE NOTE THE SUBMITTED SURVEY DOES NOT SHOW THIS
 PROPERTY IS IN AN AE FLOOD ZONE. PLEASE SUBMIT A
 CURRENT SURVEY SHOWING THE LOCATION OF THE AE FLOOD
 ZONE AND THE PROPOSED LOCATION OF THE NEW MANUFACTURED
 BUILDING. IF THE MANUFACTURED BUILDING IS IN AN AE
 FLOOD ZONE, THEN THE BOTTOM OF THE FLOOR FRAMING MUST
 BE ABOVE THE BASE FLOOD WITH THE ADDITIONAL 2 FEET
 FREEBOARD BY WEST PALM BEACH FLOOD ORDINANCES.
  
 FLOOD ZONE CERTIFICATES/ SURVEYORS- DEPT. OF
 AGRICULTURE
 ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION &
 CONTROL
 FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION
 94-546. STRUCTURE IS IN AN "A" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW
 CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN
 ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION IF PERMIT
 APPLICATION AFTER SEPT. 12/2016,
 AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE
 BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD.
 AFTER OCT. 11/ 2017 THE BUILDING DEPARTMENT WILL HAVE
 ADOPTED THE NEW FLOOD MAPS IN NAVD 88 ELEVATIONS. YOU
 CAN GO TO THE WEBSITE:
 WWW.NGS.NOAA.GOV/TOOLS/VERTCON/VERTCON.HTML FOR
 CONVERSIONS.
  
 3) THE SUBMITTED SURVEY SHOWS THE LOCATION OF THE
 MANUFACTURED BUILDING AND EXISTING BUILDING BUT DOES
 NOT PROVIDE AN ASSUMED PROPERTY LINE BETWEEN THE 2
 STRUCTURES NOR SHOW WALL AND WINDOW RATINGS BECAUSE OF
 THE CLOSENESS OF THE 2 STRUCTURES. SEE 2017 FBC-B
 SECTIONS:
 TABLE 602 FIRE RESISTANCE RATINGS FOR EXTERIOR WALLS
 BASED ON FIRE SEPARATION DISTANCE
 TABLE 705.8 FIRE SEPARATION DISTANCE AND DEGREE OF
 OPENING PROTECTIVES.
  
 4) STAIR & RAMP SHEETS 11-19ALL SHOW THEY ARE APPROVED
 IN TEXAS, THEY DO NOT SHOW A FLORIDA REGISTERED
 ENGINEER. FLORIDA STATUTE 471.
  
 5) SHEET 10 THE ACCESSIBLE RAMP SHEET INDICATES THE TOP
 LANDING IS 5 FEET 4 INCHES BY 5 FEET 4 INCHES. THE PLAN
 IS NOT CLEAR IF THIS IS A OUTSIDE MEASUREMENT OR INSIDE
 MEASUREMENT OF THE GUARDRAIL? THE TOP LANDING MUST BE A
 CLEAR LANDING OF 60 INCHES BY 60 INCHES CLEAR. 2017
 FBC-ACCESSIBILITY CODE 405.7.4.
  
 6) SHEET 10 THERE IS NO DIMENSION FROM THE LATCH SIDE
 OF THE DOOR TO THE GUARDRAIL TO THE RIGHT SIDE OF THE
 DOOR. WHEN CALIBRATING THE PLAN AND MEASURING THE
 DISTANCE FROM THE EDGE OF DOOR TO THE GUARDRAIL THERE
 APPEARS TO BE ONLY 18 INCHES. THE 2017
 FBC-ACCESSIBILITY CODE REQUIRES 2-0 FEET MANEUVERING
 CLEARANCE SEE FIGURE 404.2.4.1(H).
  
 7) SHEET 2 SHOWS THE MANUFACTURES BUILDING FLOOR PLAN
 AND NO LAYOUT OF THE STAIRS AND LANDING NOR THE RAMP
 AND TOP LANDING. THE SHEET 10 FOR THE RAMP INDICATES
 THE RAMP AND TOP LANDING ARE 35 FEET 4 INCHES LONG THE
 DISTANCE BETWEEN THE 2 DOORS IS ONLY 31.20 FEET. PLEASE
 PROVIDE THE FLOOR PLAN WITH BOTH LANDINGS FOR DOOR AND
 RAMP PLUS THE STAIR AND RAMP. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 8) PLEASE PROVIDE HOW LONG THIS UNIT IS INTENDED TO BE
 AT THIS SITE, MAY REQUIRE IMPACT FEES.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  