2020-09-01 14:04:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20081311 2277 PALM BEACH LAKES BLVD
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. PER WPB FBC 107.2.1, CLEARLY INDICATE ON PLAN SHEET
 5 OF 7 WHETHER THE PLUMBING PLAN OR THE OPTIONAL
 PLUMBING PLAN IS APPLICABLE; SANITARY AND WATER RISERS
 SHALL REFLECT THE APPLICATION.
 2. PER WPB FBC 107.2.1, CLEARLY INDICATE ON THE SURVEY
 THE METER AND BACKFLOW PREVENTER DESIGNATED TO PROVIDE
 POTABLE WATER TO THE UNIT. PROVIDE ROUTING AND SIZING
 OF WATER SERVICE TO THE POINT OF CONNECTION AT THE
 TRAILER. PROVIDE SPEC/DETAIL FOR LEAD FREE RPZ BFP.
 3. PER WPB FBC 107.2.1, CLEARLY INDICATE ON THE SURVEY
 ONE OF THE FOLLOWING;
 A. THE CAPACITY AND LOCATION OF A PORTABLE SANITARY
 HOLDING TANK
 B. PROVIDE A BUILDING SEWER AND CONNECTION TO THE CITY
 SEWAGE SYSTEM
 4. PER WPB FBC 107.2.1, CLEARLY INDICATE THE FUEL
 SOURCE AND TYPE FOR THE PORTABLE GENERATORS NOTED ON
 THE SURVEY.
  
  
 PROVISO: ACCESSIBILITY; SEE PLAN PAGE 1 OF 7
 A. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 B. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1
 C. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 D. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 E. FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6
 F. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 G. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
 H. PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT
 THE CENTER) OF THE GRIPPING SURFACE,
 I. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 J. UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2
 K. DRINKING FOUNTAINS SHALL COMPLY WITH 307 AND 602 PER
 FBC ACC 602.1.
 L. UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2.
 M. OPERABLE PARTS SHALL COMPLY WITH 309 PER FBC ACC
 602.3.
 N. SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC 602.4.
 O. THE SPOUT SHALL BE LOCATED 15 INCHES (380 MM)
 MINIMUM FROM THE VERTICAL SUPPORT AND 5 INCHES (125 MM)
 MAXIMUM FROM THE FRONT EDGE OF THE UNIT, INCLUDING
 BUMPERS PER FBC ACC 602.5.
 P. THE SPOUT SHALL PROVIDE A FLOW OF WATER 4 INCHES
 (100 MM) HIGH MINIMUM AND SHALL BE LOCATED 5 INCHES
 (125 MM) MAXIMUM FROM THE FRONT OF THE UNIT. THE ANGLE
 OF THE WATER STREAM SHALL BE MEASURED HORIZONTALLY
 RELATIVE TO THE FRONT FACE OF THE UNIT. WHERE SPOUTS
 ARE LOCATED LESS THAN 3 INCHES (75 MM) OF THE FRONT OF
 THE UNIT, THE ANGLE OF THE WATER STREAM SHALL BE 30
 DEGREES MAXIMUM. WHERE SPOUTS ARE LOCATED BETWEEN 3
 INCHES (75 MM) AND 5 INCHES (125 MM) MAXIMUM FROM THE
 FRONT OF THE UNIT, THE ANGLE OF THE WATER STREAM SHALL
 BE 15 DEGREES MAXIMUM PER FBC ACC 602.6.
 Q. SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND PER FBC ACC 607.2.
 R. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  