| 2020-09-10 09:30:01 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT-20081311 | | | | | | CODES IN EFFECT: | | | | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE DETAILS AND SPEC SHEETS OF THE | | | GENERATORS AND THE FUEL TANKS. IT MENTIONS PORTABLE | | | GENERATORS, IS THERE GOING TO BE ANY PIPING FROM TANK | | | TO GENERATORS? WHAT KIND OF TANKS ARE GOING TO BE USED? | | | HOW ARE YOU GOING TO SECURE THE TANKS? HOW ARE YOU | | | GOING TO PROTECT THE TANKS AND THE GENERATORS FROM | | | VEHICULAR TRAFFIC? THE GENERATOR AND FUEL SUPPLY SHOULD | | | BE SUBMITTED AS A SEPARATE SUBMITTAL. FBC FS 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|