| 2020-09-24 08:16:52 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20081298 |
| | 9/24/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE AN LP GAS RISER DRAWING SHOWING THE TYPES |
| | AND SIZES OF PIPING; TOTAL DEVELOPED LENGTH OF THE |
| | SYSTEM AND LENGTHS OF BRANCHES TO ALL NEW AND EXISTING |
| | LP APPLIANCES OR EQUIPMENT; TOTAL BTUH LOAD OF THE |
| | SYSTEM AND INDIVIDUAL LOADS OF APPLIANCES OR EQUIPMENT; |
| | LOCATIONS AND TYPES OF SHUTOFF VALVES, LOCATIONS AND |
| | MAKES AND MODELS OF REGULATORS INCLUDING INLET AND |
| | OUTLET PRESSURES, LOCATIONS OF UNION, RISERS AND FLEX |
| | CONNECTORS; AND A LIST OF GAS PIPE SIZING TABLES- |
| | SECTION 107.2.1 WPB. PLEASE NOTE THE UPDATED GENERAC |
| | SPECIFICATIONS INDICATE THE A 306,000 FULL BTUH LOAD |
| | FOR THE 22 KW GENERATOR. PROVIDE UPDATED SPECS AND |
| | MARKED UP SPECS FOR THE REGULATORS SHOWING THE SELECTED |
| | MODELS TO BE INSTALLED. |
| | |
| | 2) SUBMIT A SUB-PERMIT FOR THE INSTALLATION OF THE TANK |
| | AND THE PIPING- SECTION 105.1 WPB. THE SUBMITTED |
| | APPLICATIONS BEAR EC LICENCES WHICH ARE NOT VALID FOR |
| | THE LP TANK INSTALLATION. THE SUB-PERMIT APPLICATION |
| | SHALL BEAR THE CONTRACTOR'S FDACS LP GAS LICENSE |
| | NUMBER. |
| | |
| | 3) PLEASE MARK UP THE SUBMITTED SURVEY TO SHOW THE |
| | REQUIRED 10 FT. CLEARANCES DISTANCES FROM THE TANK TO |
| | THE BUILDING, AND ADJACENT PROPERTY LINES- TABLE |
| | 6.3.1.1 NFPA 58. PLEASE SHOW THE PIPING RUN ON THE |
| | SURVEY FROM THE TANK TO THE GENERATOR. |
| | |
| | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE |
| | BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED) |
| | IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE |
| | REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN |
| | SECTION 5.2.1.1 NFPA 58. |
| | |
| | 5) PROVIDE LP TANK INSTALLATION DETAILS AS OUTLINED IN |
| | THE SUBMITTED CONTRACT, AND AS REQUIRED BY NFPA 58: |
| | A) ENGINEERING FOR ANCHORING THE TANK TO PREVENT |
| | FLOTATION, COLLAPSE, OR LATERAL MOVEMENT- SECTION |
| | 6.6.1.6. PLEASE INCLUDE A FRONT AND SIDE ELEVATION VIEW |
| | THAT SHOWS THE BURIAL DEPTH, ANCHORING BASE MATERIAL, |
| | AND THE TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR |
| | STRAPS, AND THE TYPE OF PROTECTIVE SLEEVES FOR THE |
| | CABLES OR STRAPS |
| | B) SHOW HOW THE TANK WILL BE PROTECTED AGAINST |
| | CORROSION BY INSTALLATION OF A CATHODIC PROTECTION |
| | SYSTEM CONSISTING OF A SACRIFICIAL ANODE OR AN |
| | IMPRESSED CURRENT ANODE PER SECTIONS 5.2.1.11 & |
| | 6.6.6.1(I) NFPA 58. INDICATE THE TYPE OF PROTECTION AND |
| | HOW IT WILL BE TESTED- SECTION 6.17.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |