| Plan Review Notes For Permit 20081298 |
| Permit Number |
20081298 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-09-23 12:43:02 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PRE-FAB GENERATOR PAD DRAWING THAT WERE | | | SUBMITTED IS THE CORRECT ONE. HOWEVER, IT IS A COPY AND | | | AN ORIGINAL IS REQUIRED WHEN SUBMITTING FOR PUBLIC | | | RECORD. FS 471 & FAC 61G-15 SEE SIGNATURE COMMENTS. | | 2020-09-05 06:43:02 | VALUE APPEARS LOW. ESTIMATE IS FOR AN UNDERGROUND FUEL | | | TANK AND RELATED WORK. PROVIDE VALUE OF ALL LABOR AND | | | MATERIALS FOR THE GENERATOR / STRUCTURAL PAD AND | | | ELECTRICAL EQUIPMENT. CT |
|