| 2020-09-25 08:45:57 | PLAN REVIEW GENERATOR / BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. GENERATOR SPECIFICATIONS SUBMITTED FOR REVIEW ARE |
| | FOR A 2016 MODEL GENERAC 22KW GENERATOR. |
| | PROVIDE CURRENT GENERATOR SPECIFICATIONS. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 2. DESIGN PRESSURES CALCULATED ON GENERATOR PAD |
| | ENGINEERING (53.19) ARE NOT REALISTIC FOR THIS SITE AND |
| | WOULD NOT ALLOW THE PROPOSED GENERATOTR PAD WITH A |
| | MAXIMUM ALLOWABLE DESIGN PRESSURE OF (47.44) TO BE |
| | ALLOWED. |
| | MY ESTIMATED DESIGN PRESSURES FOR THIS SITE WOULD BE |
| | BASED ON VULT OF 170MPH AND VASD OF 138MPH WITH A RISK |
| | CAT. II AND EXPOSURE C PROVIDING A DESIGN PRESSURE OF |
| | 39.09 FOR PALM BEACH COUNTY. THIS WOULD ALLOW THE |
| | PROPOSED GENERATOR PAD TO BE USED. |
| | PLEASE HAVE YOUR DESIGNER RE-VISIT THESE CALCULATIONS |
| | FOR THE GENERATOR PAD. |
| | R301.2.1 WIND DESIGN CRITERIA. |
| | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| | FROM FIGURE R301.2(4). |
| | |
| | |
| | NOTICE: GENERATOR PAD ELEVATION |
| | |
| | THIS SITE IS LOCATED WITHIN A SPECIAL FLOOD HAZARD AREA |
| | (SFHA) AE WITH A BASE FLOOD ELEVATION (BFE) OF 7'-0" |
| | NAVD. THE HOUSE WAS CONSTRUCTED USING THE EXISTING BFE |
| | OF 7'-0" NGVD. |
| | LOCAL FLOODPLAIN MANAGEMENT OFFICIALS ARE REQUIRED TO |
| | ENSURE THAT ALL MACHINERY AND EQUIPMENT SERVICING THE |
| | BUILDING ARE PROTECTED FROM FLOODING PER R322.1.6 |
| | PROTECTION OF MECHANICAL, PLUMBING AND ELECTRICAL |
| | SYSTEMS. |
| | MACHINERY OR EQUIPMENT SERVICING THE BUILDING SHALL BE |
| | LOCATED AT OR ABOVE THE BASE FLOOD ELEVATION (BFE) AT |
| | TIME OF NEW RESIDENTIAL CONSTRUCTION. |
| | GENERATOR PAD SHALL BE SET AT THE FINISHED FLOOR |
| | ELEVATION OF THE RESIDENCE. (7'-0" NGVD). |
| | |
| | |
| | |
| | |
| 2020-08-31 06:57:24 | SFHA - LOCATION OF GENERATOR IS IN ZONE AE WITH A BFE |
| | 6.0 FEET. NAVD. CT |