2020-09-25 08:45:57PLAN REVIEW GENERATOR / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. GENERATOR SPECIFICATIONS SUBMITTED FOR REVIEW ARE
 FOR A 2016 MODEL GENERAC 22KW GENERATOR.
 PROVIDE CURRENT GENERATOR SPECIFICATIONS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. DESIGN PRESSURES CALCULATED ON GENERATOR PAD
 ENGINEERING (53.19) ARE NOT REALISTIC FOR THIS SITE AND
 WOULD NOT ALLOW THE PROPOSED GENERATOTR PAD WITH A
 MAXIMUM ALLOWABLE DESIGN PRESSURE OF (47.44) TO BE
 ALLOWED.
 MY ESTIMATED DESIGN PRESSURES FOR THIS SITE WOULD BE
 BASED ON VULT OF 170MPH AND VASD OF 138MPH WITH A RISK
 CAT. II AND EXPOSURE C PROVIDING A DESIGN PRESSURE OF
 39.09 FOR PALM BEACH COUNTY. THIS WOULD ALLOW THE
 PROPOSED GENERATOR PAD TO BE USED.
 PLEASE HAVE YOUR DESIGNER RE-VISIT THESE CALCULATIONS
 FOR THE GENERATOR PAD.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
  
 NOTICE: GENERATOR PAD ELEVATION
  
 THIS SITE IS LOCATED WITHIN A SPECIAL FLOOD HAZARD AREA
 (SFHA) AE WITH A BASE FLOOD ELEVATION (BFE) OF 7'-0"
 NAVD. THE HOUSE WAS CONSTRUCTED USING THE EXISTING BFE
 OF 7'-0" NGVD.
 LOCAL FLOODPLAIN MANAGEMENT OFFICIALS ARE REQUIRED TO
 ENSURE THAT ALL MACHINERY AND EQUIPMENT SERVICING THE
 BUILDING ARE PROTECTED FROM FLOODING PER R322.1.6
 PROTECTION OF MECHANICAL, PLUMBING AND ELECTRICAL
 SYSTEMS.
 MACHINERY OR EQUIPMENT SERVICING THE BUILDING SHALL BE
 LOCATED AT OR ABOVE THE BASE FLOOD ELEVATION (BFE) AT
 TIME OF NEW RESIDENTIAL CONSTRUCTION.
 GENERATOR PAD SHALL BE SET AT THE FINISHED FLOOR
 ELEVATION OF THE RESIDENCE. (7'-0" NGVD).
  
  
  
  
2020-08-31 06:57:24SFHA - LOCATION OF GENERATOR IS IN ZONE AE WITH A BFE
 6.0 FEET. NAVD. CT