| 2020-10-17 08:05:22 | PLAN REVIEW GENERATOR / BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | RE: GENERATOR SPECIFICATIONS AND PRE-CAST GENERATOR PAD |
| | ENGINEERING: |
| | |
| | |
| | 1. PROVIDE THE CURRENT 2020 SPECIFICATIONS OF PROPOSED |
| | 36KW GENERATOR. |
| | SPECIFICATIONS SUBMITTED ARE FOR A 2017 GENERAC MODEL |
| | RG038 38KW GENERATOR. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 2. PROVIDE A PRE-CAST GENERATOR PAD DESIGN WITH CORRECT |
| | DATA: |
| | 2A. WIND DESIGN REQUIREMENTS FOR THIS SITE ARE VULT |
| | 170MPH, VASD 132MPH, RISK CATEGORY II AND EXPOSURE |
| | CATEGORY C. DESIGN PRESSURE FROM TABLE IS 41.65 |
| | 2B. GENERATOR TABLE SHALL INCLUDE CORRECT MODEL OF |
| | PROPOSED GENERATOR, CORRECT WEIGHT OF GENERATOR FROM |
| | SPECIFICATIONS SUBMITTED AND CORRECT ALLOWABLE |
| | PRESSURE. |
| | CURRENT TABLE HAS MODEL QTO3624ANAX, GENERATOR WEIGHT |
| | OF 1271 LBS AND ALLOWABLE PRESSURE OF 40.50. |
| | |
| | NOTE 1: PRE-CAST GENERATOR PAD ENGINEERING REQUIRES |
| | SIGNATURE OF DESIGN PROFESSIONAL. SEE COMMENTS UNDER |
| | SIGNATURE REVIEW. |
| | |
| | NOTE 2: VALUE HAS BEEN ADJUSTED TO $18,975.00 BASED ON |
| | NEW APPLICATION SUBMITTED ON 10/08/2020. |
| | |
| | NOTE 3: TWO DOC'S IN SUPPORTING DOC'S FOLDER ARE |
| | MISLABELED: |
| | 1. SURVEY IS LABELED GENERATOR SPECIFICATIONS |
| | 2. GENERATOR SPECIFICATIONS ARE LABELED SURVEY. |
| | |
| | NOTE 4: THREE DOC'S IN DRAWINGS FOLDER ARE MISLABELED: |
| | 1. GENERATOR SPECIFICATIONS ARE LABELED GENERATOR SLAB |
| | SPECIFICATIONS |
| | 2. PROPERTY DETAIL IS LABELED BENEBY CONTRACT |
| | 3. COPY OF 1ST PERMIT APPLICATION IS LABELED BENEBY |
| | PROERTY APPRAISER |
| | |
| | WHEN RE-SUBMITTING, USE THE REQUIRED NAMING CONVENTION |
| | FOR EACH DOCUMENT |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |