2020-10-17 08:05:22PLAN REVIEW GENERATOR / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: GENERATOR SPECIFICATIONS AND PRE-CAST GENERATOR PAD
 ENGINEERING:
  
  
 1. PROVIDE THE CURRENT 2020 SPECIFICATIONS OF PROPOSED
 36KW GENERATOR.
 SPECIFICATIONS SUBMITTED ARE FOR A 2017 GENERAC MODEL
 RG038 38KW GENERATOR.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE A PRE-CAST GENERATOR PAD DESIGN WITH CORRECT
 DATA:
 2A. WIND DESIGN REQUIREMENTS FOR THIS SITE ARE VULT
 170MPH, VASD 132MPH, RISK CATEGORY II AND EXPOSURE
 CATEGORY C. DESIGN PRESSURE FROM TABLE IS 41.65
 2B. GENERATOR TABLE SHALL INCLUDE CORRECT MODEL OF
 PROPOSED GENERATOR, CORRECT WEIGHT OF GENERATOR FROM
 SPECIFICATIONS SUBMITTED AND CORRECT ALLOWABLE
 PRESSURE.
 CURRENT TABLE HAS MODEL QTO3624ANAX, GENERATOR WEIGHT
 OF 1271 LBS AND ALLOWABLE PRESSURE OF 40.50.
  
 NOTE 1: PRE-CAST GENERATOR PAD ENGINEERING REQUIRES
 SIGNATURE OF DESIGN PROFESSIONAL. SEE COMMENTS UNDER
 SIGNATURE REVIEW.
  
 NOTE 2: VALUE HAS BEEN ADJUSTED TO $18,975.00 BASED ON
 NEW APPLICATION SUBMITTED ON 10/08/2020.
  
 NOTE 3: TWO DOC'S IN SUPPORTING DOC'S FOLDER ARE
 MISLABELED:
 1. SURVEY IS LABELED GENERATOR SPECIFICATIONS
 2. GENERATOR SPECIFICATIONS ARE LABELED SURVEY.
  
 NOTE 4: THREE DOC'S IN DRAWINGS FOLDER ARE MISLABELED:
 1. GENERATOR SPECIFICATIONS ARE LABELED GENERATOR SLAB
 SPECIFICATIONS
 2. PROPERTY DETAIL IS LABELED BENEBY CONTRACT
 3. COPY OF 1ST PERMIT APPLICATION IS LABELED BENEBY
 PROERTY APPRAISER
  
 WHEN RE-SUBMITTING, USE THE REQUIRED NAMING CONVENTION
 FOR EACH DOCUMENT
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  