Plan Review Notes
Plan Review Notes For Permit 20081267
Permit Number 20081267
Review Stop B
Sequence Number 1
Notes
Date Text
2020-09-22 16:52:31PLAN REVIEW GENERATOR / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) VALUE
 CITY OF WPB CHPT. 1 VALUE
 109.3 BUILDING PERMIT VALUATIONS.
  
 1A. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK.
 1B. THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. THIS INCLUDES ALL LABOR,
 MATERIALS AND RENTALS OF EQUIPMENT TO PERFORM THE SCOPE
 OF WORK.
 1C. YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY
 THE OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 BASED ON THE INFORMATION PROVIDED, VALUE CANNOT BE
 DETERMINED AT THIS TIME.
 PLEASE INCREASE THE VALUATION ACCORDINGLY.
  
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL
  
 2) PROVIDE CURRENT GENERATOR SPECIFICATIONS. SUBMITTAL
 IS FOR A 36KW GENERATOR.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3) PROVIDE STRUCTURAL DETAIL OF GENERATOR PAD.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4) STRUCTURAL PAD DETAIL SHALL BE SIGNED BY DESIGNER.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
 5) IDENTIFY LOCATION OF GENERATOR ON SURVEY. PROVIDE
 SETBACK DIMENSIONS TO PROPERTY LINES, BUILDING AND
 BUILDING OPENINGS PER PER 107.2 CONSTRUCTION DOCUMENTS.
  
 6. PROVIDE SITE WIND LOAD CALCULATIONS.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
  
  
2020-09-04 15:32:58VALUE APPEARS LOW. CT