| 2020-11-04 12:17:25 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 20081239 |
| | W. P. B. PERMIT: 17041276 |
| | ADD: 1626 OKEECHOBEE RD. |
| | CONT: SPECTRUM RENOVATIONS LLC |
| | TEL: 561-291-8350 |
| | E-MAIL: |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: WED. NOV. 04TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST. SEMI-COMPLIED. THE SUBMITTED 2ND FLOOR |
| | PLAN NOW SHOWS THE INSTALLATION OF RADIANT DAMPERS IN |
| | THE FIRE RATED CEILING. |
| | SHEET A-14 THE 1ST FLOOR A/C PLAN STILL SHOWS THE |
| | AIRDUCT/ CEILING GRILLES PENETRATING THE RATED CEILING |
| | BUT NO NOTES STATING THE INSTALLATION OF RADIANT |
| | DAMPERS. IF THE PLAN WERE TO SHOW THE DUCTS AND GRILLES |
| | TO BE INSTALLED BETWEEN THE RATED CEILING AND DROPPED |
| | CEILING AREAS AND SOFFIT WITH THE AIR VENTS BEING SIDE |
| | WALL, BELOW THE RATED CEILING RADIANT DAMPERS WOULD NOT |
| | BE REQUIRED. THE CURRENT PROPOSED PLAN SHOWS THE AIR |
| | VENTS IN THE CEILING NEEDING RADIANT DAMPERS. |
| | |
| | 1ST REVIEW NOTES. NOTE BUILDING PLAN REVIEW ASKED THIS |
| | QUESTION IN THE 2ND OF 4 REVIEWS. 6B) 420.3 HORIZONTAL |
| | SEPARATION. FLOOR ASSEMBLIES SEPARATING DWELLING UNITS |
| | IN THE SAME BUILDINGS, FLOOR ASSEMBLIES SEPARATING |
| | SLEEPING UNITS IN THE SAME BUILDING AND FLOOR |
| | ASSEMBLIES SEPARATING DWELLING OR SLEEPING UNITS FROM |
| | OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME |
| | BUILDING SHALL BE CONSTRUCTED AS HORIZONTAL ASSEMBLIES |
| | IN ACCORDANCE WITH SECTION 711. |
| | |
| | THE ISSUED SET OF PLANS SHEET CUT SECTION ON SHEET 19 |
| | OF 31 SHOWS T 5/8 INCH TYPE X FIRE DRYWALL ATTACHED TO |
| | THE BOTTOM CHORD OF THE FLOOR ASSEMBLY MAKING A PORTION |
| | OF THE RATED HORIZONTAL ASSEMBLY. ISSUES SET OF PLANS |
| | SHEET A-14.0 SHOWS DROPPED SOFFITS FROM THE 9-FOOT-HIGH |
| | RATED CEILINGS. |
| | |
| | THE PROPOSED REVISION DOES NOT SHOW THE DROPPED SOFFIT |
| | AND PENETRATING THE RATED FLOOR ASSEMBLY. FOR THIS TYPE |
| | OF CONSTRUCTION TO PASS COMPLIANCE WOULD REQUIRE |
| | COMPLIANCE WITH 717.6.2 MEMBRANE PENETRATIONS 2014 |
| | FBC-B, ONE OF THREE METHODS. 717.6.2.1 CEILING |
| | RADIATION DAMPERS. THE SAME ISSUE OCCURS ON THE 2ND |
| | FLOOR WITH RATED CEILING. |
| | |
| | 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |