| 2020-09-02 08:37:32 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20081239 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) ACCORDING TO THE ORIGINALLY APPROVED PLANS |
| | (17041276) THERE ARE 9? CEILINGS THROUGHOUT THE FIRST |
| | FLOOR WITH DROPPED 8?HIGH CEILINGS IN PART OF THE |
| | BEDROOM AREAS AND A 8? HIGH SOFFIT IN THE KITCHEN AREA |
| | ON THE 1ST FLOOR ALLOWING THE MECHANICAL DUCTWORK TO BE |
| | INSTALLED ABOVE THE 8? CEILINGS AND BELOW THE RATED |
| | FLOOR/CEILING ASSEMBLY. THIS DRAWING INDICATES THAT THE |
| | 8? CEILINGS IN THE BEDROOM AREAS AND THE 8? SOFFIT IN |
| | THE KITCHEN HAS BEEN ELIMINATED AND THE DUCTWORK HAS |
| | BEEN INSTALLED INSIDE THE RATED ASSEMBLY WITHOUT ANY |
| | PENETRATION PROTECTION I.E. RATED DAMPERS. THIS IS NOT |
| | ALLOWED AND YOU MUST PROTECT THIS RATED ASSEMBLY AT ALL |
| | PENETRATIONS. FBC M 607.6.2 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |