Plan Review Notes
Plan Review Notes For Permit 20081232
Permit Number 20081232
Review Stop B
Sequence Number 3
Notes
Date Text
2020-11-10 09:09:44WOOD DECK
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE THE STRUCTURAL CALCULATIONS FOR THE
 GUARD RAILS TO COMPLY WITH FBC 1607.8.1.1 CONCENTRATED
 LOAD. HANDRAILS AND GUARDS SHALL BE DESIGNED TO RESIST
 A CONCENTRATED LOAD OF 200 POUNDS (0.89 KN) IN
 ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7. OR HAVE THE
 ARCHITECT OR ENGINEER WHO DESIGNED THE GUARD RAIL SIGN
 AND SEAL THE DRAWINGS.
 2) GUARD RAIL DRAWINGS SHOW ATTACHMENT TO CONCRETE -
 PLEASE PROVIDE DETAILS FOR ATTACHMENT TO WOOD.
  
 FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP
 BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS
 ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE
 REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN
 REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING
 [email protected] AND ASKING FOR THE FORM.
  