| Plan Review Notes For Permit 20081232 |
| Permit Number |
20081232 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2020-11-10 09:09:44 | WOOD DECK | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE THE STRUCTURAL CALCULATIONS FOR THE | | | GUARD RAILS TO COMPLY WITH FBC 1607.8.1.1 CONCENTRATED | | | LOAD. HANDRAILS AND GUARDS SHALL BE DESIGNED TO RESIST | | | A CONCENTRATED LOAD OF 200 POUNDS (0.89 KN) IN | | | ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7. OR HAVE THE | | | ARCHITECT OR ENGINEER WHO DESIGNED THE GUARD RAIL SIGN | | | AND SEAL THE DRAWINGS. | | | 2) GUARD RAIL DRAWINGS SHOW ATTACHMENT TO CONCRETE - | | | PLEASE PROVIDE DETAILS FOR ATTACHMENT TO WOOD. | | | | | | FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO | | | BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. | | | DRAWINGS DO NOT SHOW IN "ADOBE READER" AS | | | DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR | | | ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR | | | DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP | | | BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS | | | ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE | | | REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN | | | REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING | | | [email protected] AND ASKING FOR THE FORM. | | | |
|