| Plan Review Notes For Permit 20081232 |
| Permit Number |
20081232 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-10-16 15:33:11 | WOOD DECK | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) ARCHITECTURAL DRAWINGS SHOULD SHOW THE CODE VERSION | | | AND THE WIND DESIGN CRITERIA USED FOR DESIGN - (CODE | | | VERSION, WIND SPEED, EXPOSURE, RISK CATEGORY) FBC | | | 1603.1.4 | | | 2) DRAWINGS STATE THAT GUARD RAILS ARE NOT PART OF | | | THIS. ARE THE GUARD RAILS BEING REPLACED? IF SO PLEASE | | | PROVIDE SIGNED AND SEALED GUARD RAIL DETAILS FROM AN | | | ARCHITECT OR ENGINEER OR PROVIDE A MIAMI DADE OR | | | FLORIDA STATE PRODUCT APPROVAL FOR THE GUARD RAILS. | | | |
|