| Plan Review Notes For Permit 20081232 |
| Permit Number |
20081232 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-09-24 10:28:08 | DECK | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) DRAWINGS NEED TO BE MORE DETAILED SHOWING WHICH | | | SUPPORT BOARDS WERE REPLACED - DIMENSIONS AND LENGTH OF | | | BOARDS - ATTACHMENT OF BOARDS TO STRUCTURE (CLIP | | | DESIGNATION AND SIZE AND AMOUNT OF FASTENERS) . SHOW IF | | | RAILING IS AFFECTED. | | | 2) THE DECK IS SUBJECT TO LIVE LOADS, DEAD LOADS AND | | | WIND LOADS PER FBC R301.1 PLEASE PROVIDE THE STRUCTURAL | | | CALCULATIONS REQUIRED FOR THESE LOADS OR HAVE THE | | | DETAILS PREPARED AND SIGNED AND SEALED BY AN ARCHITECT | | | OR ENGINEER FBC R301.1.3 | | | 3) PLEASE SHOW THE WIND DESIGN DATA PER FBC R301.2.1 |
|