| Plan Review Notes For Permit 20081228 |
| Permit Number |
20081228 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-10-15 10:55:00 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) RISER SHOWS MAIN 1 OF 2 WHERE IS MAIN 2 LOCATED | | | 230.72 | | | | | | 230.72 GROUPING OF DISCONNECTS (A) GENERAL. THE TWO TO | | | SIX DISCONNECTS AS PERMITTED IN 230.71 SHALL BE | | | GROUPED. EACH DISCONNECT SHALL BE MARKED TO INDICATE | | | THE LOAD SERVED. | | | | | | 2) FAULT CURRENT CALCULATION REQUIRED FOR NEW PANELS AT | | | SERVICE. | | | | | | PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT | | | AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC | | | 110.10 | | | | | | 3) PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: | | | 8.4.2. FBC CE 405.7.1 | | | | | | |
|