| Date |
Text |
| 2020-09-15 13:26:50 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. DOMESTIC WATER RISER DIAGRAM ON P0.1 SHOWS ? INCH |
| | COLD WATER ROUTED OVERHEAD TO ICEMAKER. P3.1 PLAN VIEW |
| | SHOWS IT GOING TO A BEVERAGE DISPENSER. PER WPB FBC |
| | 107.2.1, CLARIFY. |
| | |
| | 2. DOMESTIC WATER RISER DIAGRAM ON P0.1 SHOWS ? INCH |
| | COLD WATER TO RO SYSTEM BUT NO PROVISION IS MADE IN THE |
| | SANITARY FOR WASTE DISPOSAL. PROVIDE A TRAPPED AND |
| | VENTED DEDICATED WASTE RECEPTOR TO RECEIVE THE |
| | DISCHARGE OF THE RO SYSTEM. PROVIDE AN INDIRECT WASTE |
| | WITH AN AIR GAP. COMPLY WITH FBC PL 802.2, 802.2.1 AND |
| | 802.3. |
| | |
| | 3. SANITARY RISER DIAGRAM ON P0.1 SHOWS A 2 INCH WASTE |
| | AND VENT FOR SK-1 FIXTURE. P2.1 PLAN VIEW SHOWS A FLOOR |
| | DRAIN CONNECTED TO SANITARY AS WELL AS SK-1. PER WPB |
| | FBC 107.2.1, CLARIFY AND ADVISE AS TO THE PURPOSE OF |
| | THE FLOOR DRAIN. PLEASE NOTE: |
| | A. PER FBC PL 412.2, FLOOR DRAINS SHALL HAVE REMOVABLE |
| | STRAINERS. THE FLOOR DRAIN SHALL BE CONSTRUCTED SO THAT |
| | THE DRAIN IS CAPABLE OF BEING CLEANED. ACCESS SHALL BE |
| | PROVIDED TO THE DRAIN INLET. READY ACCESS SHALL BE |
| | PROVIDED TO FLOOR DRAINS. |
| | B. PER FBC PL 802.3, FOR OTHER THAN HUB DRAINS THAT |
| | RECEIVE ONLY CLEAR-WATER WASTE AND STANDPIPES, A |
| | REMOVABLE STRAINER OR BASKET SHALL COVER THE OUTLET OF |
| | WASTE RECEPTORS. WASTE RECEPTORS SHALL NOT BE INSTALLED |
| | IN CONCEALED SPACES. WASTE RECEPTORS SHALL NOT BE |
| | INSTALLED IN PLENUMS, CRAWL SPACES, ATTICS, |
| | INTERSTITIAL SPACES ABOVE CEILINGS AND BELOW FLOORS. |
| | READY ACCESS SHALL BE PROVIDED TO WASTE RECEPTORS |
| | C. PER FBC PL 802.2.1, AN AIR GAP BETWEEN THE INDIRECT |
| | WASTE PIPE AND THE FLOOD LEVEL RIM OF THE WASTE |
| | RECEPTOR SHALL BE NOT LESS THAN TWICE THE EFFECTIVE |
| | OPENING OF THE INDIRECT WASTE PIPE. |
| | |
| | 4. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S |
| | SPECIFICATION/INSTALLATION MANUAL FOR THE INSINKERATOR |
| | FAUCET AND THE RO SYSTEM. |
| | 5. PER FBC PL 604.9, PROVIDE WATER HAMMER ARRESTOR |
| | CONFORMING TO ASSE 1010 AT THE DISHWASHER AND ICE MAKER |
| | LINES. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| | REQUIRED BY FAC AND FS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20081205 1641 WORTHINGTON RD # 410 |
| | |
| | |
| | |